Chapter 4: Using SNMP
349
Field
Description
Host
The IP address of the device(s) you want to access.
This is the address to which notifications are sent
by the SNMP agent.
Port
The port number used to access the device(s).
User ID
User name for accessing the device.
Make sure the user has the SNMP v3 access
permission.
Timeout
The interval of time, in seconds, after which a new
inform communication is resent if the first is not
received.
For example, resend a new inform
communication once every 3 seconds.
Number of Retries Specify the number of times you want to resend the
inform communication if it fails.
For example, inform communications are
resent up to 5 times when the initial
communication fails.
Security Level
Three types are available.
noAuthNoPriv - neither authentication nor
privacy protocols are needed.
AuthNoPriv - only authentication is required.
authPriv - both authentication and privacy
protocols are required.
Authentication
Protocol,
Authentication
Passphrase,
Confirm
Authentication
Passphrase
The three fields are available when the security
level is set to AuthNoPriv or authPriv.
Select the authentication protocol - MD5 or SHA
Enter the authentication passphrase
Privacy Protocol,
Privacy
Passphrase,
Confirm Privacy
Passphrase
The three fields are available when the security
level is set to authPriv.
Select the Privacy Protocol - DES or AES
Enter the privacy passphrase and then confirm
the privacy passphrase
7.
Click Save.
Содержание PMC-1000
Страница 3: ...BCM2 Series Power Meter Xerus Firmware v3 4 0 User Guide...
Страница 23: ...Chapter 1 Installation and Initial Configuration 11 Panel Wiring Example...
Страница 54: ...Chapter 1 Installation and Initial Configuration 42 Branch Circuit Details...
Страница 76: ...Chapter 2 Connecting External Equipment Optional 64...
Страница 123: ...Chapter 3 Using the Web Interface 111...
Страница 558: ...Appendix D RADIUS Configuration Illustration 546 Note If your BCM2 uses PAP then select PAP...
Страница 559: ...Appendix D RADIUS Configuration Illustration 547 10 Select Standard to the left of the dialog and then click Add...
Страница 560: ...Appendix D RADIUS Configuration Illustration 548 11 Select Filter Id from the list of attributes and click Add...
Страница 563: ...Appendix D RADIUS Configuration Illustration 551 14 The new attribute is added Click OK...
Страница 564: ...Appendix D RADIUS Configuration Illustration 552 15 Click Next to continue...
Страница 594: ...Appendix E Additional BCM2 Information 582...
Страница 612: ......