Technical description 

32 18 101 001 e 

Date: 24.10.2018 

Gyr GmbH 

 

 

 

Ultrasonic heating and cooling meter 
T230 

Residential 
 

Содержание ULTRAHEAT T230

Страница 1: ...ULTRAHEAT T230 ULTRACOLD T230 Technical description 32 18 101 001 e Date 24 10 2018 Landis Gyr GmbH Ultrasonic heating and cooling meter T230 Residential...

Страница 2: ...according to EN1434 2007 1 1 000 total range Temperature measurement Easy installation and read out Removable electronic unit Large easy readable display Flow measurement with maximum values 2 set da...

Страница 3: ..._________________________15 Previous month s values LOOP 2 ___________________________________________15 General Communication LOOP 3 __________________________________________16 Other LOOP 4 ________...

Страница 4: ...ume measurement unit two temperature sensors connected in a fixed position and an electronic unit that calculates the energy consumption from the volume and temperature differ ence This technology is...

Страница 5: ...Only install or remove the meter when the pipes are pressure less After installing the meter check the leak tightness of the sys tem Guarantee and calibration validity will lapse if the calibration r...

Страница 6: ...26 Do not open the batteries Do not bring batteries into contact with water or expose to temperatures above 80 C The meter does not have any lightning protection Ensure light ning protection via the i...

Страница 7: ...Temperature measurement range 0 180 C LCD 7 digit Optical interface Standard EN 62056 21 Communication Optional Separability Always cable length 1 5 m Temperature sensor Type Pt 500 according to EN 6...

Страница 8: ...l h mbar m3 h m3 h g 0 6 110 G 3 4 1 2 6 1 2 75 2 2 0 7 520 1 5 110 G 3 4 3 15 3 135 4 1 1 3 520 1 5 130 G1 3 15 3 135 4 1 1 3 560 2 5 130 G1 5 25 5 135 6 8 2 2 560 Tolerance of pressure loss 5 Dimens...

Страница 9: ...or forces caused by pipes or fit tings If this cannot be permanently guaranteed it is necessary to improve the point of installation or fix the lines in position by means of suitable con necting brac...

Страница 10: ...and not in the uppermost area of a pipeline This position is not permitted for cold meters and in cases where moisture can enter the electronic unit due to conden sation e g during an interruption in...

Страница 11: ...ure sensor is mounted in a protection pocket For the lower value of the temperature difference is then 5 K valid at the respective lower flow limit qi For this kind of installation the mentioned prote...

Страница 12: ...26 5 Dimension of electronic unit Fig 15 Dimensions of electronic unit Fig 16 Wall adapter view from above and side Note Wall adapter plates are available as an accessory Fig 17 Maximum screw head he...

Страница 13: ...Dimension of electronic unit 13 26 Fig 18 Wall mounting...

Страница 14: ...eter status in kWh MWh MJ or GJ Note In order to prevent reading errors the decimal places of the values displayed are marked with a frame Note Calibrated values can be recognized by an additionally d...

Страница 15: ...w Missing time Time with flow Previous month s values LOOP 2 Previous month s values Log date Energy quantity Cooling registers at the reporting date optional Volume on set day Missing time on set day...

Страница 16: ...OP 4 Other Date Time Code entry for test para operation 6 2 Monthly values The meter stores the following values for 24 months on the monthly set day Energy Volume Missing time and the maxima with dat...

Страница 17: ...the decimal point of a value is based on the chosen measurement path and the chosen dimension 8 Power supply The meter is equipped with batteries Options 6 years battery 11 years battery kWh MWh MJ G...

Страница 18: ...utput The pulse exit permits the output of pulses that can be derived from the ener gy the volume or the error status Two channels are available whose functions can be parameterized with the service s...

Страница 19: ...g Stationary data reading User defined data reading 20 s 15 min Acc to telegram length 12 900 s 1 Open Metering System 2 May vary depending on terrain and building structure Data telegram F000 station...

Страница 20: ...sec battery life time 11 years Following data are available by default for data reading Current energy Energy previous month on reference date Monthly reference date Energy previous year on reference...

Страница 21: ...ured Air in the measurement unit pipe bleed air from line delivery condi tion F1 Interruption in the hot side temperature sensor Inform service department F2 Interruption in the cold side temperature...

Страница 22: ...ak Republic Slovakian SK Dial plate for Uzbekistan Russian UZ 5 Manufacturer s label Code Logo Landis Gyr 00 Other labels on request xx 6 Sensor type and method of connection Code Sensor Pt500 not rem...

Страница 23: ...The unique encryption key for every meter will be created and you will get a file by email meter number encryption key 1 Stationary radio Ordering example battery life 6 years data telegram F000 T230...

Страница 24: ...Bus 24 26 Ordering example battery life 11 years data telegram F002 T230 XXXX XXXX X XX FE XXX F001 20 sec encryption F battery life 11 years E wireless M Bus function F002 mobile data reading 20 seco...

Страница 25: ...110 G 3 4 75 2 2 A 1 5 110 130 G G1 135 4 1 B 2 5 130 G1 135 6 8 C The indicated pressure loss of a flow sensor is at the nominal flowrate qp Using the Kv Factor which defines the flow rate at a press...

Страница 26: ...Landis Gyr GmbH Humboldtstrasse 64 90459 Nuremberg Germany...