Chapter 5: Using the Command Line Interface
477
Example - Default Upper Thresholds for Temperature
It is assumed that your preferred measurement unit for temperature is
set to degrees Celsius. Then the following command sets the default
Upper Warning threshold to 20 and Upper Critical threshold to 24
for all temperature sensors.
config:#
defaultThresholds temperature upperWarning 20
upperCritical 24
Sensor Threshold Configuration Commands
A sensor configuration command begins with
sensor. You can use the
commands to configure the threshold, hysteresis and assertion timeout
values for any sensor associated with the following items:
Outlets
Inlets
Inlet poles (for three-phase PDUs only)
Overcurrent protectors
Environmental sensors
It is permitted to assign a new value to the threshold at any time
regardless of whether the threshold has been enabled.
Commands for Outlet Sensors
A sensor configuration command for outlets begins with
sensor outlet.
You can configure various outlet sensor threshold settings at a time by
combining multiple commands. See
Multi-Command Syntax
(on page
Set the Upper Critical threshold for an outlet sensor:
config:#
sensor outlet <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an outlet sensor:
config:#
sensor outlet <n> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an outlet sensor:
Содержание PMC-1000
Страница 3: ...BCM2 Series Power Meter Xerus Firmware v3 4 0 User Guide...
Страница 23: ...Chapter 1 Installation and Initial Configuration 11 Panel Wiring Example...
Страница 54: ...Chapter 1 Installation and Initial Configuration 42 Branch Circuit Details...
Страница 76: ...Chapter 2 Connecting External Equipment Optional 64...
Страница 123: ...Chapter 3 Using the Web Interface 111...
Страница 558: ...Appendix D RADIUS Configuration Illustration 546 Note If your BCM2 uses PAP then select PAP...
Страница 559: ...Appendix D RADIUS Configuration Illustration 547 10 Select Standard to the left of the dialog and then click Add...
Страница 560: ...Appendix D RADIUS Configuration Illustration 548 11 Select Filter Id from the list of attributes and click Add...
Страница 563: ...Appendix D RADIUS Configuration Illustration 551 14 The new attribute is added Click OK...
Страница 564: ...Appendix D RADIUS Configuration Illustration 552 15 Click Next to continue...
Страница 594: ...Appendix E Additional BCM2 Information 582...
Страница 612: ......