Chapter 4: Using SNMP
346
To enable SNMP notifications:
1.
Choose Device Settings > Network Services > SNMP.
2.
In the SNMP Notifications section, enable the SNMP notification
feature, and configure related fields. For details, refer to:
SNMPv2c Notifications
(on page 346)
SNMPv3 Notifications
(on page 347)
Note: Any changes made to the 'SNMP Notifications' section on the
SNMP page will update the settings of the System SNMP Notification
Action, and vice versa. See
Available Actions
(on page 250).
SNMPv2c Notifications
1.
Choose Device Settings > Network Services > SNMP.
2.
In the SNMP Agent, make sure the Enable SNMP v1/v2c checkbox is
selected.
3.
In the SNMP Notifications section, make sure the Enable SNMP
Notifications checkbox is selected.
4.
Select SNMPv2c Trap or SNMPv2c Inform as the notification type.
5.
Type values in the following fields.
Содержание PMC-1000
Страница 3: ...BCM2 Series Power Meter Xerus Firmware v3 4 0 User Guide...
Страница 23: ...Chapter 1 Installation and Initial Configuration 11 Panel Wiring Example...
Страница 54: ...Chapter 1 Installation and Initial Configuration 42 Branch Circuit Details...
Страница 76: ...Chapter 2 Connecting External Equipment Optional 64...
Страница 123: ...Chapter 3 Using the Web Interface 111...
Страница 558: ...Appendix D RADIUS Configuration Illustration 546 Note If your BCM2 uses PAP then select PAP...
Страница 559: ...Appendix D RADIUS Configuration Illustration 547 10 Select Standard to the left of the dialog and then click Add...
Страница 560: ...Appendix D RADIUS Configuration Illustration 548 11 Select Filter Id from the list of attributes and click Add...
Страница 563: ...Appendix D RADIUS Configuration Illustration 551 14 The new attribute is added Click OK...
Страница 564: ...Appendix D RADIUS Configuration Illustration 552 15 Click Next to continue...
Страница 594: ...Appendix E Additional BCM2 Information 582...
Страница 612: ......