4.30 Inadvertent Energization (ANSI 50/27)
445
7UM62 Manual
C53000-G1176-C149-3
4.30
Inadvertent Energization (ANSI 50/27)
Setting Ranges/
Resolutions
Overcurrent Pick-Up
I
STAGE
0.5 A to 100.0 A
1
) (Increments 0.5 A)
1
)
or
∞
(does not expire)
Release
U
1
<
10.0 V to 125.0 V (Increments 0.1 V)
Delay Time
PICK UP T U
1
<
0.00 s to 60.00 s (Increments 0.01 s)
or
∞
(does not expire)
Drop Out Delay Time
DROP OUT T U
1
< 0.00 s to 60.00 s (Increments 0.01 s)
or
∞
(does not expire)
Inherent Operating
Times
– Pickup Times
Approx. 25 ms
– Dropout Times
Approx. 35 ms
Dropout
I>>>
Approx. 0.80 or 250 mA
1
)
Release Threshold
U
1
<
Approx. 1.05
Tolerances
Overcurrent pick-up
I>>>
5 % of setting value or 100 mA
1
)
Release
U
1
<
1 % of setting value or 0.5 V
Delay Times
T
1 % of setting value or 10 ms
Influencing
Variables
Power Supply DC Voltage (U
DC
) in Range
0.8
≤
U
PS
/ U
PS nominal
≤
1.15
1%
Temperature in Range
23 °F
≤ ϑ
amb
≤
131 °F
0.3 % / 10 °F
–5 °C
≤ ϑ
amb
≤
55 °C
0.5 % / 10 K
Frequency in Range
0.95
≤
f/f
N
≤
1.05
1 %
Harmonic currents
– Up to 10 % 3. Harmonic
< 1 %
– Up to 10 % 5. Harmonic
< 1 %
1
) For I
N
= 1 A, divide all limits and increments by 5.