A.12 Settings
537
7UM62 Manual
C53000-G1176-C149-3
5301
100% SEF-PROT.
100% Stator-
Earth-Fault Pro-
tection
OFF
ON
Block relay for trip
commands
OFF
100% Stator-Earth-Fault
Protection
5302
R< SEF ALARM
100% Stator-
Earth-Fault Pro-
tection
20..700 Ohm
100 Ohm
Pickup Value of Alarm
Stage Rsef<
5303
R<< SEF TRIP
100% Stator-
Earth-Fault Pro-
tection
20..700 Ohm
20 Ohm
Pickup Value of Tripping
Stage Rsef<<
5304
T SEF ALARM
100% Stator-
Earth-Fault Pro-
tection
0.00..60.00 sec;
∞
10.00 sec
Time Delay of Alarm Stage
Rsef<
5305
T SEF TRIP
100% Stator-
Earth-Fault Pro-
tection
0.00..60.00 sec;
∞
1.00 sec
Time Delay of Tripping
Stage Rsef<<
5306
SEF I>>
100% Stator-
Earth-Fault Pro-
tection
0.02..1.50 A
0.40 A
Pickup Value of I SEF>>
Stage
5307
U20 MIN
100% Stator-
Earth-Fault Pro-
tection
0.3..15.0 V
1.0 V
Supervision Threshold of
20Hz Voltage
5308
I20 MIN
100% Stator-
Earth-Fault Pro-
tection
5..40 mA
10 mA
Supervision Threshold of
20Hz Current
5309
PHI I SEF
100% Stator-
Earth-Fault Pro-
tection
-60..60
°
0
°
Correction Angle for I SEF
100%
5310A SEF Rps
100% Stator-
Earth-Fault Pro-
tection
0.0..700.0 Ohm
0.0 Ohm
Resistance Rps
5311A Rl-PARALLEL
100% Stator-
Earth-Fault Pro-
tection
20..700 Ohm;
∞
∞
Ohm
Parallel Load Resistance
6001
ROTOR E/F
Rotor Earth
Fault Protection
OFF
ON
Block relay for trip
commands
OFF
Rotor Earth Fault Protec-
tion (R, fn)
6002
RE< WARN
Rotor Earth
Fault Protection
3.0..30.0 kOhm
10.0 kOhm
Pickup Value of Warning
Stage Re<
6003
RE<< TRIP
Rotor Earth
Fault Protection
1.0..5.0 kOhm
2.0 kOhm
Pickup Value of Tripping
Stage Re<<
6004
T-WARN-RE<
Rotor Earth
Fault Protection
0.00..60.00 sec;
∞
10.00 sec
Time Delay of Warning
Stage Re<
6005
T-TRIP-RE<<
Rotor Earth
Fault Protection
0.00..60.00 sec;
∞
0.50 sec
Time Delay of Tripping
Stage Re<<
6006
X COUPLING
Rotor Earth
Fault Protection
-100..800 Ohm
398 Ohm
Coupling Reactance
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments