Thermal Overload Protection (ANSI 49)
63
7UM62 Manual
C53000-G1176-C149-3
The following trip times result for different ambient temperatures
Θ
K
with a supposed
load current of I = 1.5
⋅
I
N, device
and a preload I
pre
= 0
2.9.2.1
Thermal Overload Protection Settings
The following list indicates the setting ranges and the default settings of an I
N
= 1 A
secondary nominal current. For a secondary nominal current of I
N
= 5 A, these values
must be multiplied by 5. Consider the current transformer ratios when setting the
device with primary values.
t
600 s
1.5
1.1
--------
è
ø
æ
ö
2
40 °C
40 °C
–
1.1
2
100 °C
⋅
------------------------------------
0
–
+
1.5
1.1
--------
è
ø
æ
ö
2
40 °C
40 °C
–
1.1
2
100 °C
⋅
------------------------------------
1
–
+
---------------------------------------------------------------------
ln
⋅
è
ø
ç
÷
ç
÷
ç
÷
ç
÷
æ
ö
463 s
≈
=
with
Θ
K
= 40 °C:
t
600 s
1.5
1.1
--------
è
ø
æ
ö
2
80 °C
40 °C
–
1.1
2
100 °C
⋅
------------------------------------
0
–
+
1.5
1.1
--------
è
ø
æ
ö
2
80 °C
40 °C
–
1.1
2
100 °C
⋅
------------------------------------
1
–
+
---------------------------------------------------------------------
ln
⋅
è
ø
ç
÷
ç
÷
ç
÷
ç
÷
æ
ö
366 s
≈
=
with
Θ
K
= 80 °C:
t
600 s
1.5
1.1
--------
è
ø
æ
ö
2
0 °C
40 °C
–
1.1
2
100 °C
⋅
----------------------------------
0
–
+
1.5
1.1
--------
è
ø
æ
ö
2
0 °C
40 °C
–
1.1
2
100 °C
⋅
----------------------------------
1
–
+
-------------------------------------------------------------------
ln
⋅
è
ø
ç
÷
ç
÷
ç
÷
ç
÷
æ
ö
637 s
≈
=
with
Θ
K
= 0 °C:
Addr.
Setting Title
Setting Options
Default Setting
Comments
1601
Ther. OVER LOAD
OFF
ON
Block relay for trip com-
mands
Alarm Only
OFF
Thermal Overload Protection
1602
K-FACTOR
0.10..4.00
1.11
K-Factor
1603
TIME CONSTANT
30..32000 sec
600 sec
Thermal Time Constant
1604
Θ
ALARM
70..100 %
90 %
Thermal Alarm Stage
1610A
I ALARM
0.10..4.00 A
1.00 A
Current Overload Alarm Setpoint
1612A
K
τ
-FACTOR
1.0..10.0
1.0
Kt-Factor when Motor Stops
1615A
I MAX THERM.
0.50..8.00 A
3.30 A
Maximum Current for Thermal
Replica
1616A
T EMERGENCY
10..15000 sec
100 sec
Emergency Time
1605
TEMP. RISE I
40..200
°
C
100
°
C
Temperature Rise at Rated Sec.
Curr.
1606
TEMP. RISE I
104..392
°
F
212
°
F
Temperature Rise at Rated Sec.
Curr.