![Siemens SIPROTEC 7UM62 Manual Download Page 545](http://html.mh-extra.com/html/siemens/siprotec-7um62/siprotec-7um62_manual_382677545.webp)
A.12 Settings
529
7UM62 Manual
C53000-G1176-C149-3
2110
I-REF>
Restricted Earth
Fault Protection
0.05..2.00 I/InO
0.10 I/InO
I-REF> Pickup
2112
T I-REF>
Restricted Earth
Fault Protection
0.00..60.00 sec;
∞
0.00 sec
T I-REF> Time Delay
2113A SLOPE
Restricted Earth
Fault Protection
0.00..0.95
0.25
Slope of Charac. I-REF> =
f(I0-Rest)
2114A BASE POINT
Restricted Earth
Fault Protection
0.00..2.00 I/InO
0.00 I/InO
Base Point for Slope of
Characteristic
3001
UNDEREXCIT.
Underexcitation
Protection
OFF
ON
Block relay for trip
commands
OFF
Underexcitation Protection
3002
1/xd CHAR. 1
Underexcitation
Protection
0.25..3.00
0.41
Conductance Intersect
Characteristic 1
3003
ANGLE 1
Underexcitation
Protection
50..120
°
80
°
Inclination Angle of Charac-
teristic 1
3004
T CHAR. 1
Underexcitation
Protection
0.00..60.00 sec;
∞
10.00 sec
Characteristic 1 Time Delay
3005
1/xd CHAR. 2
Underexcitation
Protection
0.25..3.00
0.36
Conductance Intersect
Characteristic 2
3006
ANGLE 2
Underexcitation
Protection
50..120
°
90
°
Inclination Angle of Charac-
teristic 2
3007
T CHAR. 2
Underexcitation
Protection
0.00..60.00 sec;
∞
10.00 sec
Characteristic 2 Time Delay
3008
1/xd CHAR. 3
Underexcitation
Protection
0.25..3.00
1.10
Conductance Intersect
Characteristic 3
3009
ANGLE 3
Underexcitation
Protection
50..120
°
90
°
Inclination Angle of Charac-
teristic 3
3010
T CHAR 3
Underexcitation
Protection
0.00..60.00 sec;
∞
0.30 sec
Characteristic 3 Time Delay
3011
T SHRT Uex<
Underexcitation
Protection
0.00..60.00 sec;
∞
0.50 sec
T-Short Time Delay (Char.
& Uexc<)
3012
EXCIT. VOLT.
Underexcitation
Protection
ON
OFF
OFF
State of Excitation Volt.
Supervision
3013
Uexcit. <
Underexcitation
Protection
0.50..8.00 V
2.00 V
Excitation Voltage Superv.
Pickup
3014A Umin
Underexcitation
Protection
10.0..125.0 V
25.0 V
Undervoltage blocking Pik-
kup
3101
REVERSE
POWER
Reverse Power
Protection
OFF
ON
Block relay for trip
commands
OFF
Reverse Power Protection
3102
P> REVERSE
Reverse Power
Protection
-30.00..-0.50 %
-1.93 %
P> Reverse Pickup
3103
T-SV-OPEN
Reverse Power
Protection
0.00..60.00 sec;
∞
10.00 sec
Time Delay Long (without
Stop Valve)
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments