Earth Current Differential Protection (ANSI 87GN, TN)
105
7UM62 Manual
C53000-G1176-C149-3
2.13.2.1 Settings of the Earth Current Differential Protection
2.13.2.2 Information for the Earth Current Differential Protection
Addr.
Setting Title
Setting Options
Default Setting
Comments
2101
REF PROT.
OFF
ON
Block relay for trip com-
mands
OFF
Restricted Earth Fault Protection
2102
REF I> BLOCK
1.0..2.5 I/InO
1.5 I/InO
REF Pickup of Phase Current
Blocking
2103
REF U0>RELEASE
1.0..100.0 V; 0
5.0 V
REF Pickup of U0> Release
2110
I-REF>
0.05..2.00 I/InO
0.10 I/InO
I-REF> Pickup
2112
T I-REF>
0.00..60.00 sec;
∞
0.00 sec
T I-REF> Time Delay
2113A
SLOPE
0.00..0.95
0.25
Slope of Charac. I-REF> = f(I0-
Rest)
2114A
BASE POINT
0.00..2.00 I/InO
0.00 I/InO
Base Point for Slope of Charac-
teristic
F.No.
Alarm
Comments
05803 >BLOCK REF
>BLOCK restricted earth fault prot.
05811 REF OFF
Restricted earth fault is switched OFF
05812 REF BLOCKED
Restricted earth fault is BLOCKED
05813 REF ACTIVE
Restricted earth fault is ACTIVE
05840 REF I> blocked
REF is blocked by phase current
05841 REF U0> releas.
REF Release by U0>
05817 REF picked up
REF protection picked up
05821 REF TRIP
REF protection TRIP
05836 REF Adap.fact.
REF: adverse Adaption factor CT
05847 I0-Diff:
I0-Diff at REF-Trip
05848 I0-Res:
I0-Restraint at REF-Trip