Functions
274
7UM62 Manual
C53000-G1176-C149-3
9035
RTD 3 STAGE 2
-50..250
°
C;
∞
120
°
C
RTD 3: Temperature Stage 2
Pickup
9036
RTD 3 STAGE 2
-58..482
°
F;
∞
248
°
F
RTD 3: Temperature Stage 2
Pickup
9041A
RTD 4 TYPE
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 4: Type
9042A
RTD 4 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 4: Location
9043
RTD 4 STAGE 1
-50..250
°
C;
∞
100
°
C
RTD 4: Temperature Stage 1
Pickup
9044
RTD 4 STAGE 1
-58..482
°
F;
∞
212
°
F
RTD 4: Temperature Stage 1
Pickup
9045
RTD 4 STAGE 2
-50..250
°
C;
∞
120
°
C
RTD 4: Temperature Stage 2
Pickup
9046
RTD 4 STAGE 2
-58..482
°
F;
∞
248
°
F
RTD 4: Temperature Stage 2
Pickup
9051A
RTD 5 TYPE
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 5: Type
9052A
RTD 5 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 5: Location
9053
RTD 5 STAGE 1
-50..250
°
C;
∞
100
°
C
RTD 5: Temperature Stage 1
Pickup
9054
RTD 5 STAGE 1
-58..482
°
F;
∞
212
°
F
RTD 5: Temperature Stage 1
Pickup
9055
RTD 5 STAGE 2
-50..250
°
C;
∞
120
°
C
RTD 5: Temperature Stage 2
Pickup
9056
RTD 5 STAGE 2
-58..482
°
F;
∞
248
°
F
RTD 5: Temperature Stage 2
Pickup
9061A
RTD 6 TYPE
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 6: Type
9062A
RTD 6 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 6: Location
Addr.
Setting Title
Setting Options
Default Setting
Comments