Breaker Control
305
7UM62 Manual
C53000-G1176-C149-3
Control Logic using
CFC
For Zone Controlled (field interlocking), control logic can be developed, using the
CFC. Via specific release conditions the information “released” or “zone controlled” is
available.
Switching
Authority
Switching authority configures the relay to perform Local/Remote Supervisory
functions. The command source having switching authority can be set in the
interlocking condition “Switching authority”. The following switching authority ranges
are defined in the following priority sequence:
−
LOCAL (commands are issued from the relay keyboard)
−
DIGSI
®
4
−
REMOTE (commands are issued from SCADA)
The switching authority condition
LOCAL
allows commands from the user inter-
face of the relay, but not remote or DIGSI commands. In the 7UM62, the options
“Local” and “Remote” are available in the display after entering a password.
The switching authority condition
DIGSI
allows commands to be initiated using
DIGSI
®
4. Commands are allowed for both a remote and a local DIGSI
®
4
connection. When a (local or remote) DIGSI PC logs on to the device, it enters
its Virtual Device Number (VD). The device only accepts commands having that
VD (with switching authority = OFF or REMOTE). When the DIGSI PC logs off,
the VD is cancelled.
Commands are checked for their source and the device settings, and compared
to the information set in the objects “Switching authority” and “Switching authority
DIGSI”.
Configuration Programming:
1) Switching authority: y/n
(create appropriate object)
2) Switching authority DIGSI
®
4: y/n
(create appropriate object)
3) Specific object (e.g., switching device): Switching authority LOCAL (check for
commands initiated locally via keypad): y/n
4) Specific object (e.g., switching device): Switching authority REMOTE (check for
SAS, REMOTE, or DIGSI commands): y/n