4.34 Operating Ranges of the Protection Functions
455
7UM62 Manual
C53000-G1176-C149-3
4.34
Operating Ranges of the Protection Functions
Table 4-1
Operating Ranges of the Protection Functions
Operat. cond. 0
Operational condition 1
Operat. cond. 0
Protection function
f
≤
10 Hz
11 Hz
<
f/Hz
≤
40 40 Hz
≤
f/Hz
≤
69
f
≥
70 Hz
Definite-time overcurrent prot. (50, 51, 67)
active
active
active
active
Inverse-time overcurrent protection (51V)
inactive
active
active
inactive
Thermal overload protection (49)
inactive
1
)
active
active
inactive
1)
Unbalanced load protection (46)
inactive
1
)
active
active
inactive
1)
Startup overcurrent protection (51)
active
inactive
inactive
active
Differential protection (87G/87T)
active
active
active
active
Earth current differential protection (87GN/TN)
inactive
active
active
inactive
Underexcitation protection (40)
inactive
active
active
inactive
Reverse power protection (32R)
inactive
active
active
inactive
Forward power supervision (32F)
inactive
active
active
inactive
Impedance protection (21)
inactive
active
active
inactive
Out–of–step protection (78)
inactive
active
active
inactive
Undervoltage protection (27)
inactive
2)
active
active
inactive
2)
Overvoltage protection (59)
active
active
active
active
Overfrequency protection (81/O)
inactive
active
active
inactive
3)
Underfrequency protection (81/U)
inactive
active
active
inactive
Overexcitation protection U/f> (24)
inactive
1
)
active
active
inactive
1
)
Inverse undervoltage protection (27)
inactive
2)
active
active
inactive
2
)
Rate-of-frequency-change protection (81R)
inactive
active
4
)
active
inactive
Jump of voltage vector
inactive
active
5
)
active
5
)
inactive
90–% Stator earth fault prot. (59N, 64G, 67G)
active
active
active
active
Sensitive earth fault protection (51GN, 64F)
inactive
active
active
inactive
100–% S/E/F with 3rd harm. (27TN, 59TN)
inactive
active
active
inactive
100–% stator earth fault protection(20 Hz)
(64G)
active
active
active
active
Rotor earth fault protection (64R)
active
active
active
active
Rotor earth fault protection (64R)
active
active
active
active
Motor starting time supervision (48)
inactive
active
active
inactive
Restart inibit for motors (66, 49
Rotor
)
inactive
active
active
inactive
Breaker Failure Protection (50BF)
inactive
active
active
inactive
Inadvertent energization (50/27)
active
active
active
active
DC voltage protection (59N
DC
, 51N
DC
)
active
active
active
active
Threshold Monitoring
inactive
active
active
inactive
External trip coupling
active
active
active
active
Temperature detection by thermoboxes
active
active
active
active