Underexcitation (Loss-of-Field) Protection (ANSI 40)
109
7UM62 Manual
C53000-G1176-C149-3
Figure 2-53
Logic diagram of the Underexcitation Protection
2.14.2 Setting Hints
General
The underexcitation protection is only effective and accessible if this function was set
within the framework of the protective function configuration (section 2.2, address
,
=
Enabled
). Set
Disabled
if the function is not required. At
the address
the user can switch the function
ON
or
OFF
, or only
block the trip command (
Block Relay
).
The correct power system data is required according to section 2.3. This is a
prerequisite for the setting of the underexcitation protection.
OR
&
ANGLE 1
FNo. 05329
ANGLE 2
FNo. 05330
ANGLE 3
FNo. 05327
FNo. 05328
FNo. 05323
&
&
FNo. 05337
FNo. 05344
FNo. 05345
FNo. 05343
FNo. 05334
FNo. 05332
Tripping
matrix
&
FNo. 05346
FNo.05336
OR
OR
TMin
TRIP CMD