Functions
112
7UM62 Manual
C53000-G1176-C149-3
Voltage transformer: U
N VT prim
= 6.3 kV
Multiplied by a safety factor of about 1.05, the setting value
at address
results.
For
α
1
, the angle of the underexcitation limiting of the voltage regulator is selected or
the inclination angle of the machine stability characteristic is used. The setting value
is typically situated between 60 ° and 80 °.
In most cases, the machine manufacturer prescribes a minimum excitation value for
small active powers. For this purpose, characteristic 1 is cut from characteristic 2 in
case of a low active-power load. Consequently,
is set to about 0.9
⋅
), the
to 90 °. The kinked tripping limit according to figure
2-54 (CHAR. 1, CHAR. 2) results in this way, if the corresponding time delays
and
of both characteristics are set equally.
Characteristic 3 serves to adapt the protection to the dynamic machine stability limits.
If there are no precise indications, the user must select a value
situated approximately between the synchronous direct reactance x
d
and the transient
reactance x
d
'. However, it should be greater than 1.
A value between 80 ° and 110 ° is usually selected for the corresponding
,
which ensures that only a dynamic instability can lead to a pickup with characteristic
3. The associated time delay is set at address
to the value suggested
in Table 2-6.
Figure 2-56
Admittance Diagram of a Turbo Generator
Time Delays
If the static limit curve consisting of the characteristics 1 and 2 is exceeded, the voltage
regulator must first have the opportunity of enhancing the excitation. For this reason,
a warning message due to this criterion is ”long-time” delayed (at least 10 s for
and
If the excitation voltage is missing or too low, the stator criterion picks up as well,
provided that the excitation voltage request feature has been switched
ON
at address
, and the voltage has dropped below the threshold
set at address
, or the absence of the excitation voltage has been signalled to
the device by a binary input. In all these cases tripping is possible with a short delay.
1
x
dsec
-------------
1
2.47
-----------
483 A
6300 V
-------------------
6300 V
500 A
-------------------
⋅
⋅
0.39
=
=
Simulated
characteristic
Underexcitation limitation
(controller)
ϕ
Ν
θ
Ν
I
E
U
N
--------
1
x
d
-------
I
N
U
N
--------
consists of
characteristic 1
and char. 2
1.05
⋅
1
x
d
-------
G [p.u.]
B [p.u.]