Functions
150
7UM62 Manual
C53000-G1176-C149-3
2.19.2.1 Settings of the Undervoltage Protection
2.19.2.2 Information for the Undervoltage Protection
Addr.
Setting Title
Setting Options
Default Setting
Comments
4001
UNDERVOLTAGE
OFF
ON
Block relay for trip com-
mands
OFF
Undervoltage Protection
4002
U<
10.0..125.0 V
75.0 V
U< Pickup
4003
T U<
0.00..60.00 sec;
∞
3.00 sec
T U< Time Delay
4004
U<<
10.0..125.0 V
65.0 V
U<< Pickup
4005
T U<<
0.00..60.00 sec;
∞
0.50 sec
T U<< Time Delay
4006A
U< DOUT RATIO
1.01..1.20
1.05
U< Drop Out Ratio
F.No.
Alarm
Comments
06503 >BLOCK U/V
>BLOCK undervoltage protection
06506 >BLOCK U<
>BLOCK undervoltage protection U<
06508 >BLOCK U<<
>BLOCK undervoltage protection U<<
06530 Undervolt. OFF
Undervoltage protection switched OFF
06531 Undervolt. BLK
Undervoltage protection is BLOCKED
06532 Undervolt. ACT
Undervoltage protection is ACTIVE
06533 U< picked up
Undervoltage U< picked up
06537 U<< picked up
Undervoltage U<< picked up
06539 U< TRIP
Undervoltage U< TRIP
06540 U<< TRIP
Undervoltage U<< TRIP