Functions
296
7UM62 Manual
C53000-G1176-C149-3
SETTINGS
menu. Waveform capture makes a distinction between the trigger for an
oscillographic record and the criterion to save the record (address
). Normally the trigger is the pickup of a protective element, i.e.
when a protective element picks up the time is 0. The criterion for saving can be the
pickup as well (
Save w. Pickup
), or the device trip (
Save w. TRIP
). Another
option is to set (
Start with TRIP
). A trip command issued by the device is both the
trigger and the criterion to save the record with this setting.
A waveform capture includes in machine protection always the complete course of a
fault. An oscillographic fault record includes data recorded prior to the time of trigger,
and data after the dropout of the recording criterion. Therefore address
0402
is preset to
Fault event
.
The user determines the length of pre-trigger time and post-dropout time to be
included in the fault record with the settings in address
and
address
. The maximum length of time of a record
is entered at address
. The setting depends on the criterion for storage,
the delay time of the protective functions and the desired number of stored fault
events. The largest value here is 5 s for fault recording of instantaneous values, 80 s
for recording of r.m.s. values (see address
). A total of 8 records can be saved.
Note: These times apply for 50 Hz. They will be different with another frequency. If
RMS values
are stored, the times stated for parameters
0403
to
will be 16
times longer.
An oscillographic record can be triggered and saved by a change in status of a binary
input or via the operator interface connected to a PC. The trigger is dynamic. The
length of a record for these special triggers is set at address
(upper bound is
, address
). Pre-trigger and post-
dropout times are not included. If the binary input time is set to
∞
, then the length of
the record equals the time that the binary input is activated (static), or the
(address
), whichever is shorter.
2.45.6.1 Settings for Oscillographic Fault Recording
2.45.6.2 Information for the Oscillographic Fault Recording
Addr.
Setting Title
Setting Options
Default Setting
Comments
401
WAVEFORMTRIG-
GER
Save with Pickup
Save with TRIP
Start with TRIP
Save with Pickup
Waveform Capture
402
WAVEFORM DATA
Fault event
Power System fault
Fault event
Scope of Waveform Data
403
MAX. LENGTH
0.30..5.00 sec
1.00 sec
Max. length of a Waveform Cap-
ture Record
404
PRE. TRIG. TIME
0.05..4.00 sec
0.20 sec
Captured Waveform Prior to
Trigger
405
POST REC. TIME
0.05..0.50 sec
0.10 sec
Captured Waveform after Event
406
BinIn CAPT.TIME
0.10..5.00 sec;
∞
0.50 sec
Capture Time via Binary Input
F.No.
Alarm
Comments
00004 >Trig.Wave.Cap.
>Trigger Waveform Capture