4.33 Additional Functions
451
7UM62 Manual
C53000-G1176-C149-3
Range
0 mA to 22.5 mA
Minimum Threshold (Limit of Validity:)
0.0 mA to 5.0 mA (Increments 0.1 mA)
Maximum Threshold
22.0 mA (fixed)
Configurable Reference Value 20 mA
10.0 % to 1000.0 %(Increments 0.1 %)
Measured Values
Supervision
Current Asymmetry
I
max
/I
min
> I - balance factor, for
I > I - balance limit. Factor and limit are
adjustable.
Voltage Asymmetry
U
max
/U
min
> U - balance factor, for
U > U - balance limit. Factor and limit are
adjustable.
Current Sum
| i
L1
+ i
L2
+ i
L3
| > I - sum threshold value,
adjustable.
Voltage Sum
|U
L1
+ U
L2
+ U
L3
+ k
U
· U
E
| > SUM.thres. U,
with k
U
= Uph/Udelta
Current Phase Sequence
Clockwise (L
1
, L
2
, L
3
)/
counter-clockwise (L
1
, L
3
, L
2
)
Voltage Phase Sequence
Clockwise (L
1
, L
2
, L
3
)/
counter-clockwise (L
1
, L
3
, L
2
)
Limit Value Monitor
Can be configured with CFC
I
L
< Limit value LV (ANSI 37-1)
Trip Log
Recording of indication of the last 8 power system faults
Time Stamping
Resolution for Event Log
1 ms
(Operational Messages)
Resolution for Trip Log (Fault Records)
1 ms
Time Deviation (Internal Clock)
Maximum 0.01 %
Buffer Battery
Lithium Battery, 3 V / 1 Ah, type CR 1/2 AA
Self-discharging time > 5 years
Message “Fail Battery” if
battery charge is low