Functions
240
7UM62 Manual
C53000-G1176-C149-3
For analog output B1 at location”B” (port B1):
At address
the percent value to be displayed at 20 mA,
At address
the smallest valid value.
For analog output B2 at location”B” (port B2):
At address
the percent value to be displayed at 20 mA,
At address
the smallest valid value.
For analog output D1 at location”D” (port D1):
At address
the percent value to be displayed at 20 mA,
At address
the smallest valid value.
For analog output D2 at location”D” (port D2):
At address
the percent value to be displayed at 20 mA,
At address
the smallest valid value.
The maximum possible value is 22.0 mA; in case of an overflow (value outside the
maximum permissible range) 22.5 mA is output.
Example:
You want to output the positive sequence currents at analog output B1, location”B”.
10 mA are the value at nominal operational current, consequently 20 mA mean
200 %. Values below 1 mA are invalid.
Settings
Address
20 mA (B1) = 200.0
%,
Address
=
1.0
mA.
2.37.3 Settings of the Analog Outputs
Addr.
Setting Title
Setting Options
Default Setting
Comments
7301
20 mA (B1) =
10.0..1000.0 %
200.0 %
20 mA (B1) correspond to
7302
MIN VALUE (B1)
0.0..5.0 mA
1.0 mA
Output value (B1) valid from
7303
20 mA (B2) =
10.0..1000.0 %
200.0 %
20 mA (B2) correspond to
7304
MIN VALUE (B2)
0.0..5.0 mA
1.0 mA
Output value (B2) valid from
7305
20 mA (D1) =
10.0..1000.0 %
200.0 %
20 mA (D1) correspond to
7306
MIN VALUE (D1)
0.0..5.0 mA
1.0 mA
Output value (D1) valid from
7307
20 mA (D2) =
10.0..1000.0 %
200.0 %
20 mA (D2) correspond to
7308
MIN VALUE (D2)
0.0..5.0 mA
1.0 mA
Output value (D2) valid from