4.1 General Device Data
399
7UM62 Manual
C53000-G1176-C149-3
For Panel Surface-
Mounted Case
On the case bottom
– Optical Wavelength
λ
= 820 nm
– Laser Class 1 Under EN 60825–1/ –2 using glass fiber 50/125 µm or
using glass fiber 62.5/125 µm
– Optical Link Signal Attenuation
Max. 8 dB, with glass fiber 62.5/125 µm
– Channel Distance
Max. 1.5 km (0.95 miles)
– Character Idle State
selectable: factory setting “Light off”
Profibus RS485 (DP)
– Connection for Flush Mounted Case
rear panel, installation location “B“
9-pin DSUB Port RS 485
For Panel Surface-
At the terminal on the case bottom
Mounted Case
– Test Voltage
500 V AC
Transmission Speed
up to 12 M Baud
– Maximum Distance of Transmission
1 km / 3280 feet / 0.62 mile at
≤
93.75 kBd
500 m /1640 feet / 0.31 mile at
≤
187.5 kBd
200 m / 660 feet at
≤
1.5 MBd
100 m/ 330 feet at
≤
12 MBd
DNP3.0 RS485
– Connection for Flush-Mounted Case
rear panel, mounting location “B“
9-pin DSUB Port RS 485
For Panel Surface-
Mounted Case
on the case bottom
– Test Voltage
500 VAC
– Transmission Speed
up to 19200 Baud
– Maximum Distance of Transmission
1 km / 3280 feet / 0.62 mile
MODBUS RS485
– Connection for Flush-Mounted Case
rear panel, mounting location “B“
9-pin DSUB Port RS 485
For Panel Surface-
Mounted Case
on the case bottom
– Test Voltage
500 VAC
– Transmission Speed
up to 19200 Baud
– Maximum Distance of Transmission
1 km / 3280 feet / 0.62 mile
Profibus Fibre Optical Link (DP)
– Connection
ST–Connector,
for FMS single ring or twin ring, depending
on order; for DP only double ring
For Flush-Mounted Case
rear panel, mounting location “B“
For Panel Surface-
Mounted Case
On the case bottom
– Transmission Speed
Up to 1.5 M Baud
Recommended:
> 500 k Baud