Functions
300
7UM62 Manual
C53000-G1176-C149-3
Check Sequence
•
Command Entry (e.g. using the keypad on the local user interface of the device)
−
Check password
→
Access rights
−
Check Switching Mode (interlocking activated/deactivated
→
Selection of
Deactivated Interlocking Recognition
•
User configurable Interlocking checks
−
Switching Authority
−
Device Position (scheduled vs. actual comparison)
−
Zone Controlled/Field Interlocking/ (logic using CFC)
−
System Interlocking (centrally, using SCADA system or substation controller)
−
Double Operation (interlocking against parallel switching operation)
−
Protection Blocking (blocking of switching operations by protective functions)
•
Fixed Command Checks
−
Internal process time (software watch dog which checks the time for processing
the control action between initiation of the control and final close of the relay
contact.
−
Setting Modification in Process (if setting modification is in process, commands
are denied or delayed)
−
Equipment Present at Output (If a circuit breaker or other operable equipment is
not configured to a binary output, then the command is denied)
−
Output Block (if an output block has been programmed for the circuit breaker,
and is active at the moment the command is processed, then the command is
denied)
−
Component Hardware Malfunction
−
Command in Progress (only one command can be processed at a time for one
circuit breaker or switch)
−
1-of-n-check (for schemes with multiple assignments, such as common ground,
whether a command has already been initiated for the affected output relay is
checked).
Monitoring the
Command
Execution
−
Interruption of a Command because of a Cancel Command
−
Running Time Monitor (feedback message monitoring time)
2.46.3 Interlocking
Interlocking checks in a SICAM
®
/SIPROTEC
®
system are divided into:
•
System Interlocking (checked by a central control system such as SCADA or
substation controller)
•
Zone Controlled/Bay Interlocking (checked in the device)
Zone Controlled/Bay Interlocking
System interlocking relies on the system data base in the substation or central control
system.