![Siemens SIPROTEC 7UM62 Manual Download Page 562](http://html.mh-extra.com/html/siemens/siprotec-7um62/siprotec-7um62_manual_382677562.webp)
A Appendix
546
7UM62 Manual
C53000-G1176-C149-3
9071A RTD 7 TYPE
RTD-Box
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 7: Type
9072A RTD 7 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 7: Location
9073
RTD 7 STAGE 1
RTD-Box
-50..250
°
C;
∞
100
°
C
RTD 7: Temperature Stage
1 Pickup
9074
RTD 7 STAGE 1
RTD-Box
-58..482
°
F;
∞
212
°
F
RTD 7: Temperature Stage
1 Pickup
9075
RTD 7 STAGE 2
RTD-Box
-50..250
°
C;
∞
120
°
C
RTD 7: Temperature Stage
2 Pickup
9076
RTD 7 STAGE 2
RTD-Box
-58..482
°
F;
∞
248
°
F
RTD 7: Temperature Stage
2 Pickup
9081A RTD 8 TYPE
RTD-Box
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 8: Type
9082A RTD 8 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 8: Location
9083
RTD 8 STAGE 1
RTD-Box
-50..250
°
C;
∞
100
°
C
RTD 8: Temperature Stage
1 Pickup
9084
RTD 8 STAGE 1
RTD-Box
-58..482
°
F;
∞
212
°
F
RTD 8: Temperature Stage
1 Pickup
9085
RTD 8 STAGE 2
RTD-Box
-50..250
°
C;
∞
120
°
C
RTD 8: Temperature Stage
2 Pickup
9086
RTD 8 STAGE 2
RTD-Box
-58..482
°
F;
∞
248
°
F
RTD 8: Temperature Stage
2 Pickup
9091A RTD 9 TYPE
RTD-Box
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 9: Type
9092A RTD 9 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 9: Location
9093
RTD 9 STAGE 1
RTD-Box
-50..250
°
C;
∞
100
°
C
RTD 9: Temperature Stage
1 Pickup
9094
RTD 9 STAGE 1
RTD-Box
-58..482
°
F;
∞
212
°
F
RTD 9: Temperature Stage
1 Pickup
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments