A Appendix
530
7UM62 Manual
C53000-G1176-C149-3
3104
T-SV-CLOSED
Reverse Power
Protection
0.00..60.00 sec;
∞
1.00 sec
Time Delay Short (with
Stop Valve)
3105A T-HOLD
Reverse Power
Protection
0.00..60.00 sec;
∞
0.00 sec
Pickup Holding Time
3201
FORWARD
POWER
Forward Power
Supervision
OFF
ON
Block relay for trip
commands
OFF
Forward Power Supervision
3202
Pf<
Forward Power
Supervision
0.5..120.0 %
9.7 %
P-forw.< Supervision Pik-
kup
3203
Pf>
Forward Power
Supervision
1.0..120.0 %
96.6 %
P-forw.> Supervision Pik-
kup
3204
T-Pf<
Forward Power
Supervision
0.00..60.00 sec;
∞
10.00 sec
T-P-forw.< Time Delay
3205
T-Pf>
Forward Power
Supervision
0.00..60.00 sec;
∞
10.00 sec
T-P-forw.> Time Delay
3206A MEAS. METHOD
Forward Power
Supervision
Method accurate
Method fast
Method accurate
Method of Operation
3301
IMPEDANCE
PROT.
Impedance Pro-
tection
OFF
ON
Block relay for trip
commands
OFF
Impedance Protection
3302
IMP I>
Impedance Pro-
tection
0.10..20.00 A
1.35 A
Fault Detection I> Pickup
3303
U< SEAL-IN
Impedance Pro-
tection
ON
OFF
OFF
State of Undervoltage Seal-
in
3304
U<
Impedance Pro-
tection
10.0..125.0 V
80.0 V
Undervoltage Seal-in Pik-
kup
3305
T-SEAL-IN
Impedance Pro-
tection
0.10..60.00 sec
4.00 sec
Duration of Undervoltage
Seal-in
3306
ZONE Z1
Impedance Pro-
tection
0.05..130.00 Ohm
2.91 Ohm
Impedance Zone Z1
3307
T-Z1
Impedance Pro-
tection
0.00..60.00 sec;
∞
0.10 sec
Impedance Zone Z1 Time
Delay
3308
ZONE Z1B
Impedance Pro-
tection
0.05..65.00 Ohm
4.99 Ohm
Impedance Zone Z1B
3309
T-Z1B
Impedance Pro-
tection
0.00..60.00 sec;
∞
0.10 sec
Impedance Zone Z1B Time
Delay
3310
ZONE Z2
Impedance Pro-
tection
0.05..65.00 Ohm
4.16 Ohm
Impedanz Zone Z2
3311
ZONE2 T2
Impedance Pro-
tection
0.00..60.00 sec;
∞
0.50 sec
Impedance Zone Z2 Time
Delay
3312
T END
Impedance Pro-
tection
0.00..60.00 sec;
∞
3.00 sec
T END: Final Time Delay
3313
POWER SWING
Impedance Pro-
tection
ON
OFF
OFF
Power Swing Blocking
Addr.
Setting Title
Function
Setting Options
Default Setting