A.12 Settings
541
7UM62 Manual
C53000-G1176-C149-3
8107
BAL. FACT. I S2
Measurement
Supervision
0.10..0.90
0.50
Balance Factor for Current
Monitor S2
8108
SUM.thres. U
Measurement
Supervision
10..200 V
10 V
Summation Thres. for Volt.
Monitoring
8109
SUM.Fact. U
Measurement
Supervision
0.60..0.95; 0
0.75
Factor for Volt. Sum. Moni-
toring
8110
Σ
I THRESHOLD S1 Measurement
Supervision
0.05..2.00 A
0.10 A
Summated Cur. Mon.
Threshold on Side 1
8111
Σ
I FACTOR S1
Measurement
Supervision
0.00..0.95
0.10
Summated Current Mon.
Factor on Side 1
8112
Σ
I THRESHOLD S2 Measurement
Supervision
0.05..2.00 A
0.10 A
Summated Cur. Mon.
Threshold on Side 2
8113
Σ
I FACTOR S2
Measurement
Supervision
0.00..0.95
0.10
Summated Current Mon.
Factor on Side 2
8201
TRIP Cir. SUP.
Trip Circuit
Supervision
OFF
ON
OFF
TRIP Circuit Supervision
8501
MEAS. VALUE 1>
Threshold
supervision
Disabled
Active Power P
Reactive Power Q
Change of Active
Power Delta P
Positive Sequence
Voltage U1
Negative Sequence
Voltage U2
Zero Sequence Cur-
rent I0
Positive Sequence
Current I1
Negative Sequence
Current I2
Power Angle PHI
Disabled
Measured Value for Thres-
hold MV1>
8502
THRESHOLD
MV1>
Threshold
supervision
-200..200 %
100 %
Pickup Value of Measured
Value MV1>
8503
MEAS. VALUE 2<
Threshold
supervision
Disabled
Active Power P
Reactive Power Q
Change of Active
Power Delta P
Positive Sequence
Voltage U1
Negative Sequence
Voltage U2
Zero Sequence Cur-
rent I0
Positive Sequence
Current I1
Negative Sequence
Current I2
Power Angle PHI
Disabled
Measured Value for Thres-
hold MV2<
8504
THRESHOLD
MV2<
Threshold
supervision
-200..200 %
100 %
Pickup Value of Measured
Value MV2<
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments