Functions
54
7UM62 Manual
C53000-G1176-C149-3
2.8.2.2
Information for the Inverse-Time Overcurrent Protection
1406
ANSI CURVE
Very Inverse
Inverse
Moderately Inverse
Extremely Inverse
Definite Inverse
Very Inverse
ANSI Curve
1407
VOLT. INFLUENCE
without
Voltage controlled
Voltage restraint
without
Voltage Influence
1408
U<
10.0..125.0 V
75.0 V
U< Threshold for Release Ip
Addr.
Setting Title
Setting Options
Default Setting
Comments
F.No.
Alarm
Comments
01883 >BLOCK O/C Ip
>BLOCK inverse O/C time protection
01891 O/C Ip OFF
O/C protection Ip is switched OFF
01892 O/C Ip BLOCKED
O/C protection Ip is BLOCKED
01893 O/C Ip ACTIVE
O/C protection Ip is ACTIVE
01896 O/C Ip Fault L1
O/C fault detection Ip phase L1
01897 O/C Ip Fault L2
O/C fault detection Ip phase L2
01898 O/C Ip Fault L3
O/C fault detection Ip phase L3
01899 O/C Ip pick.up
O/C Ip picked up
01900 O/C Ip TRIP
O/C Ip TRIP