3.2 Checking Connections and System (Plant) Integration
345
7UM62 Manual
C53000-G1176-C149-3
When the voltage on the binary input connected to this auxiliary contact is removed,
the message “
” should appear in the Event Log. When the
voltage is restored, the message “
OFF” should occur. If one of
these messages does not appear, then the connections and the configuration settings
should be checked. If the ON and OFF messages are exchanged, then the breaker
auxiliary contact type should be checked and corrected if necessary.