A Appendix
540
7UM62 Manual
C53000-G1176-C149-3
7201
DC PROTECTION
DC Voltage/
Current Protec-
tion
OFF
ON
Block relay for trip
commands
OFF
DC Voltage/Current Protec-
tion
7202
MEAS.METHOD
DC Voltage/
Current Protec-
tion
Mean Value
Root Mean Square
Mean Value
Measurement Method
(MEAN/RMS Values)
7203
DC >/<
DC Voltage/
Current Protec-
tion
DC Voltage/Current
Stage DC >
DC Voltage/Current
Stage DC <
DC Voltage/Current
Stage DC >
Method of Operation (DC >/
<)
7204
U DC ><
DC Voltage/
Current Protec-
tion
0.1..8.5 V
2.0 V
DC Voltage Pickup
7205
I DC ><
DC Voltage/
Current Protec-
tion
0.2..17.0 mA
4.0 mA
DC Current Pickup
7206
T DC
DC Voltage/
Current Protec-
tion
0.00..60.00 sec;
∞
2.00 sec
Time Delay for Trip of DC
Protection
7301
20 mA (B1) =
Analog Outputs
10.0..1000.0 %
200.0 %
20 mA (B1) correspond to
7302
MIN VALUE (B1)
Analog Outputs
0.0..5.0 mA
1.0 mA
Output value (B1) valid
from
7303
20 mA (B2) =
Analog Outputs
10.0..1000.0 %
200.0 %
20 mA (B2) correspond to
7304
MIN VALUE (B2)
Analog Outputs
0.0..5.0 mA
1.0 mA
Output value (B2) valid
from
7305
20 mA (D1) =
Analog Outputs
10.0..1000.0 %
200.0 %
20 mA (D1) correspond to
7306
MIN VALUE (D1)
Analog Outputs
0.0..5.0 mA
1.0 mA
Output value (D1) valid
from
7307
20 mA (D2) =
Analog Outputs
10.0..1000.0 %
200.0 %
20 mA (D2) correspond to
7308
MIN VALUE (D2)
Analog Outputs
0.0..5.0 mA
1.0 mA
Output value (D2) valid
from
8001
FUSE FAIL MON.
Supervision
OFF
ON
OFF
Fuse Failure Monitor
8101
MEASURE.
SUPERV
Measurement
Supervision
OFF
ON
OFF
Measurement Supervision
8102
BALANCE U-LIMIT
Measurement
Supervision
10..100 V
50 V
Voltage Threshold for
Balance Monitoring
8103
BAL. FACTOR U
Measurement
Supervision
0.58..0.90
0.75
Balance Factor for Voltage
Monitor
8104
BAL. I LIMIT S1
Measurement
Supervision
0.10..1.00 A
0.50 A
Current Balance Monitor
Side 1
8105
BAL. FACT. I S1
Measurement
Supervision
0.10..0.90
0.50
Balance Factor for Current
Monitor S1
8106
BAL. I LIMIT S2
Measurement
Supervision
0.10..1.00 A
0.50 A
Current Balance Monitor
Side 2
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments