![Siemens SIPROTEC 7UM62 Manual Download Page 561](http://html.mh-extra.com/html/siemens/siprotec-7um62/siprotec-7um62_manual_382677561.webp)
A.12 Settings
545
7UM62 Manual
C53000-G1176-C149-3
9042A RTD 4 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 4: Location
9043
RTD 4 STAGE 1
RTD-Box
-50..250
°
C;
∞
100
°
C
RTD 4: Temperature Stage
1 Pickup
9044
RTD 4 STAGE 1
RTD-Box
-58..482
°
F;
∞
212
°
F
RTD 4: Temperature Stage
1 Pickup
9045
RTD 4 STAGE 2
RTD-Box
-50..250
°
C;
∞
120
°
C
RTD 4: Temperature Stage
2 Pickup
9046
RTD 4 STAGE 2
RTD-Box
-58..482
°
F;
∞
248
°
F
RTD 4: Temperature Stage
2 Pickup
9051A RTD 5 TYPE
RTD-Box
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 5: Type
9052A RTD 5 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 5: Location
9053
RTD 5 STAGE 1
RTD-Box
-50..250
°
C;
∞
100
°
C
RTD 5: Temperature Stage
1 Pickup
9054
RTD 5 STAGE 1
RTD-Box
-58..482
°
F;
∞
212
°
F
RTD 5: Temperature Stage
1 Pickup
9055
RTD 5 STAGE 2
RTD-Box
-50..250
°
C;
∞
120
°
C
RTD 5: Temperature Stage
2 Pickup
9056
RTD 5 STAGE 2
RTD-Box
-58..482
°
F;
∞
248
°
F
RTD 5: Temperature Stage
2 Pickup
9061A RTD 6 TYPE
RTD-Box
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 6: Type
9062A RTD 6 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 6: Location
9063
RTD 6 STAGE 1
RTD-Box
-50..250
°
C;
∞
100
°
C
RTD 6: Temperature Stage
1 Pickup
9064
RTD 6 STAGE 1
RTD-Box
-58..482
°
F;
∞
212
°
F
RTD 6: Temperature Stage
1 Pickup
9065
RTD 6 STAGE 2
RTD-Box
-50..250
°
C;
∞
120
°
C
RTD 6: Temperature Stage
2 Pickup
9066
RTD 6 STAGE 2
RTD-Box
-58..482
°
F;
∞
248
°
F
RTD 6: Temperature Stage
2 Pickup
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments