Functions
250
7UM62 Manual
C53000-G1176-C149-3
Address
determines the voltage threshold above which the
summation voltage monitoring picks (see Figure 2-117) (absolute component,
referred only to U
N
). The relative component for pickup of the summation voltage
monitoring (Figure 2-117) is set at address
.
Measuring Voltage
Failure Detection
The measuring voltage failure monitoring is only effective and accessible if it has been
set during configuration of the protection functions at address
=
Enabled
. Set
Disabled
if the function is not required. Address
is used to switch the function
ON
or
OFF
.
The thresholds U
2
/U
1
≥
40 % and I
2
/I
1
≤
20 % for detecting 1-pole and 2-pole voltage
failures are fixed. The thresholds for detecting a 3-pole voltage failure (undervoltage
threshold = 10 V, below which the failure detection feature responds unless the
current changes significantly, and the differential current monitoring = 0.5 I
N
) are
likewise fixed and need not be set.
2.38.2.1 Settings
The following list indicates the setting ranges and the default settings of a I
N
= 1 A
secondary nominal current. For a secondary nominal current of I
N
= 5 A, these values
must be multiplied by 5. Consider the current transformer ratios when setting the
device with primary values.
Note:
In the power system data 1, the voltage earth path and its matching factor
have been specified. The measured value monitoring will only function
properly if the settings there are correct.
Addr.
Setting Title
Setting Options
Default Setting
Comments
8001
FUSE FAIL MON.
OFF
ON
OFF
Fuse Failure Monitor
Addr.
Setting Title
Setting Options
Default Setting
Comments
8101
MEASURE.
SUPERV
OFF
ON
OFF
Measurement Supervision
8102
BALANCE U-LIMIT
10..100 V
50 V
Voltage Threshold for Balance
Monitoring
8103
BAL. FACTOR U
0.58..0.90
0.75
Balance Factor for Voltage
Monitor
8104
BAL. I LIMIT S1
0.10..1.00 A
0.50 A
Current Balance Monitor Side 1
8105
BAL. FACT. I S1
0.10..0.90
0.50
Balance Factor for Current Moni-
tor S1
8106
BAL. I LIMIT S2
0.10..1.00 A
0.50 A
Current Balance Monitor Side 2
8107
BAL. FACT. I S2
0.10..0.90
0.50
Balance Factor for Current Moni-
tor S2
8108
SUM.thres. U
10..200 V
10 V
Summation Thres. for Volt.
Monitoring