Functions
232
7UM62 Manual
C53000-G1176-C149-3
Figure 2-112 illustrates the course of events during an unwanted connection in case
of a machine standstill and, contrary to this, during a voltage collapse in case of a short
circuit close to generator terminals.
Figure 2-112 Course of Events of the Inadvertent Energizing Protection
2.35.2.1 Settings of the Inadvertent Energizing Protection
The following list indicates the setting ranges and the default settings of a I
N
= 1 A
secondary nominal current. For a secondary nominal current of I
N
= 5 A, these values
must be multiplied by 5.
2.35.2.2 Information for the Inadvertent Energizing Function
Trip
I
L
>
Release of
U
1
<
Machine
”stopped”
Inadvertent
energization
T U1<
Dropout
T U1<
Pickup
a) Trip after inadvertent energization
b) Unit connection
Machine
”running”
Short circ.
close to gen.
Trip
Start T U1
Pickup
INADV. EN.
short-circuit
protection
Addr.
Setting Title
Setting Options
Default Setting
Comments
7101
INADVERT. EN.
OFF
ON
Block relay for trip com-
mands
OFF
Inadvertent Energisation
7102
I STAGE
0.1..20.0 A;
∞
0.3 A
I Stage Pickup
7103
RELEASE U1<
10.0..125.0 V; 0
50.0 V
Release Threshold U1<
7104
PICK UP T U1<
0.00..60.00 sec;
∞
5.00 sec
Pickup Time Delay T U1<
7105
DROP OUT T U1<
0.00..60.00 sec;
∞
1.00 sec
Drop Out Time Delay T U1<
F.No.
Alarm
Comments
05533 >BLOCK I.En.
>BLOCK inadvertent energ. prot.
05541 I.En. OFF
Inadvert. Energ. prot. is swiched OFF
05542 I.En. BLOCKED
Inadvert. Energ. prot. is BLOCKED