A.12 Settings
525
7UM62 Manual
C53000-G1176-C149-3
402
WAVEFORM
DATA
Oscillographic
Fault Records
Fault event
Power System fault
Fault event
Scope of Waveform Data
403
MAX. LENGTH
Oscillographic
Fault Records
0.30..5.00 sec
1.00 sec
Max. length of a Waveform
Capture Record
404
PRE. TRIG. TIME
Oscillographic
Fault Records
0.05..4.00 sec
0.20 sec
Captured Waveform Prior
to Trigger
405
POST REC. TIME
Oscillographic
Fault Records
0.05..0.50 sec
0.10 sec
Captured Waveform after
Event
406
BinIn CAPT.TIME
Oscillographic
Fault Records
0.10..5.00 sec;
∞
0.50 sec
Capture Time via Binary
Input
1108
ACTIVE POWER
Power System
Data 2
Generator
Motor
Generator
Measurement of Active
Power for
1201
O/C I>
O/C I> (with
undervoltage
seal-in)
OFF
ON
Block relay for trip
commands
OFF
Overcurrent Time Protec-
tion I>
1202
I>
O/C I> (with
undervoltage
seal-in)
0.05..20.00 A
1.35 A
I> Pickup
1203
T I>
O/C I> (with
undervoltage
seal-in)
0.00..60.00 sec;
∞
3.00 sec
T I> Time Delay
1204
U< SEAL-IN
O/C I> (with
undervoltage
seal-in)
ON
OFF
OFF
State of Undervoltage Seal-
in
1205
U<
O/C I> (with
undervoltage
seal-in)
10.0..125.0 V
80.0 V
Undervoltage Seal-in Pik-
kup
1206
T-SEAL-IN
O/C I> (with
undervoltage
seal-in)
0.10..60.00 sec
4.00 sec
Duration of Undervoltage
Seal-in
1207A I> DOUT RATIO
O/C I> (with
undervoltage
seal-in)
0.90..0.99
0.95
I> Drop Out Ratio
1301
O/C I>>
O/C I>> (with
direction)
OFF
ON
Block relay for trip
commands
OFF
Overcurrent Time Protec-
tion I>>
1302
I>>
O/C I>> (with
direction)
0.05..20.00 A
4.30 A
I>> Pickup
1303
T I>>
O/C I>> (with
direction)
0.00..60.00 sec;
∞
0.10 sec
T I>> Time Delay
1304
Phase Direction
O/C I>> (with
direction)
Forward
Reverse
Reverse
Phase Direction
1305
LINE ANGLE
O/C I>> (with
direction)
-90..90
°
60
°
Line Angle
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments