A Appendix
490
7UM62 Manual
C53000-G1176-C149-3
Figure A-28 Block Connection with Isolated Starpoint
Connection on each side to three current transformers and three voltage transformers (phase-to-earth volt-
ages). Differential protection function only used for the generator;
Detection of displacement voltage at a broken delta winding (e–n).
R18
R16
R17
R15
J8
J7
R13
R14
Q1
Q2
Q3
Q4
Q5
Q6
7UM62
Earthing transformer
with measuring winding
Yd5
R
L
J1
J2
J3
J4
J5
J6
Q8
Q7
TD3
K18
K17 +
TD1
K14
K13 +
TD2
K16
K15 +
Divider
3PP1326
V
Exc.
For 100 % stator
earth fault protection
I
EE2
I
EE1
A (L1)
B (L2)
C (L3)
V
A(L1)
V
B(L2)
V
C(L3)
V
E
I
A(L1)S1
I
B(L2)S1
I
C(L3)S1
I
A(L1)S2
I
B(L2)S2
I
C(L3)S2
Measuring transducer:
- Temperature
injection
- or DC voltage
injection
Rotor earth-current
injection
ANSI
52
Excitation
n
e