A Appendix
538
7UM62 Manual
C53000-G1176-C149-3
6007
R SERIES
Rotor Earth
Fault Protection
0..999 Ohm
50 Ohm
Series Resistance (e.g.
Meas. Brushes)
6008
I RE<
Rotor Earth
Fault Protection
1.0..50.0 mA; 0
2.0 mA
Pickup Value of Failure
Detection Ire<
6009
PHI I RE
Rotor Earth
Fault Protection
-15.0..15.0
°
0.0
°
Correction Angle for Ire
6101
REF 1-3Hz
Rotor Earth
Fault Protec-
tion (1-3Hz)
OFF
ON
Block relay for trip
commands
OFF
Rotor Earth Fault Protec-
tion (1-3Hz)
6102
RE< WARN
Rotor Earth
Fault Protec-
tion (1-3Hz)
5.0..80.0 kOhm
40.0 kOhm
Pickup Value of Warning
Stage Re<
6103
RE<< TRIP
Rotor Earth
Fault Protec-
tion (1-3Hz)
1.0..10.0 kOhm
5.0 kOhm
Pickup Value of Tripping
Stage Re<<
6104
T-WARN-RE<
Rotor Earth
Fault Protec-
tion (1-3Hz)
0.00..60.00 sec;
∞
10.00 sec
Time Delay of Warning
Stage Re<
6105
T-TRIP-RE<<
Rotor Earth
Fault Protec-
tion (1-3Hz)
0.00..60.00 sec;
∞
1.00 sec
Time Delay of Tripping
Stage Re<<
6106
Qc <
Rotor Earth
Fault Protec-
tion (1-3Hz)
0.00..1.00 mAs
0.02 mAs
Pickup Value of open Rotor
Circuit (Qc)
6107A TEST RESISTOR
Rotor Earth
Fault Protec-
tion (1-3Hz)
1.0..10.0 kOhm
3.3 kOhm
Testing Resistor
6501
STARTUP MOTOR Motor Starting
Time Supervi-
sion
OFF
ON
Block relay for trip
commands
OFF
Motor Starting Time Super-
vision
6502
START. CURRENT Motor Starting
Time Supervi-
sion
0.10..16.00 A
3.12 A
Starting Current of Motor
6503
STARTING TIME
Motor Starting
Time Supervi-
sion
1.0..180.0 sec
8.5 sec
Starting Time of Motor
6504
LOCK ROTOR
TIME
Motor Starting
Time Supervi-
sion
0.5..120.0 sec;
∞
6.0 sec
Permissible Locked Rotor
Time
6505
I MOTOR START
Motor Starting
Time Supervi-
sion
0.60..10.00 A
1.60 A
Current Pickup Value of
Motor Starting
6601
RESTART INHIBIT
Restart Inhibit
for Motors
OFF
ON
Block relay for trip
commands
OFF
Restart Inhibit for Motors
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments