Functions
64
7UM62 Manual
C53000-G1176-C149-3
2.9.2.2
Information List for the Thermal Overload Protection
1607
TEMP. INPUT
Disabled
4-20 mA
Fieldbus
Temp. of RTD 1
Disabled
Temperature Input
1608
TEMP. SCAL.
40..300
°
C
100
°
C
Temperature for Scaling
1609
TEMP. SCAL.
104..572
°
F
212
°
F
Temperature for Scaling
F.No.
Alarm
Comments
01503 >BLK ThOverload
>BLOCK thermal overload protection
01506 >RM th.rep. O/L
>Reset memory for thermal replica O/L
01507 >Emer.Start O/L
>Emergency start O/L
01508 >Fail.Temp.inp
>Failure temperature input
01511 Th.Overload OFF
Thermal Overload Protection OFF
01512 Th.Overload BLK
Thermal Overload Protection BLOCKED
01513 Overload ACT
Overload Protection ACTIVE
01514 Fail.Temp.inp
Failure temperature input
01519 RM th.rep. O/L
Reset memory for thermal replica O/L
01515 O/L I Alarm
Overload Current Alarm (I alarm)
01516 O/L
Θ
Alarm
Thermal Overload Alarm
01517 O/L Th. pick.up
Thermal Overload picked up
01521 ThOverload TRIP
Thermal Overload TRIP
Addr.
Setting Title
Setting Options
Default Setting
Comments