4.24 100–% Stator Earth Fault Protection with 20 Hz Voltage Injection (ANSI 64G, –100 %)
439
7UM62 Manual
C53000-G1176-C149-3
4.24
100–% Stator Earth Fault Protection with 20 Hz Voltage Injection
(ANSI 64G, –100 %)
Setting Ranges/
Resolution
Alarm Stage R
SEF
<
20 to 700
Ω
(Increments 1
Ω)
Tripping Stage R
SEF
<<
20 to 700
Ω
(Increments 1
Ω)
Earth Currrent StageI
SEF
>
0.02 to 1.50 A
(Increments 0.01 A)
Delay Time
0.00 to 60.00 s
(Increments 0.01 s
or
∞
(does not expire))
Supervision Threshold of 20 HZ Voltage
U20
0.3 to 15.0 V
(Increments 0.1 V)
I20
5 to 40 mA
(Increments 1 mA)
Correction Angle
–60° to +60°
(Increments 1°)
Inherent Operating
Times
Pickup Time R
SEF
<, R
SEF
<<
≤
1.3 s
Pickup Time I
SEF
>
≤
250 ms
Dropout Time R
SEF
<, R
SEF
<<
≤
0.8 s
Dropout Time I
SEF
>
≤
120 s
Dropout
Dropout/Pickup Ratio
Approx. 1.2 to 1.7
Tolerances
Resistance
Approx. 5 % or 2
Ω
Current
3 % or 3 mA
Delay Time
1 % or 10 ms
Influencing
Variables for
Pickup
Power Supply Direct Voltage in Range
0.8
≤
U
H
/U
HN
≤
1.15
≤
1 %
Temperature in Range
–5 °C
≤ ϑ
amb
≤
55 °C
≤
0.5 %/10 K
Frequency in Range
0.95
≤
f/f
N
≤
1.05
≤
1 %
Harmonics
– Up to 10 % 3rd Harmonics
≤
1 %
– Up to 10 % 5th Harmonics
≤
1 %