Restart Inhibit for Motors (ANSI 66, 49Rotor)
221
7UM62 Manual
C53000-G1176-C149-3
is used to switch the function
ON
or
OFF
, or to block only the trip
command (
Block Relay
).
Necessary
Characteristic
Values
The user communicates to the protective relay the characteristic motor values
supplied by the manufacturer, which are necessary for calculation of the rotor
temperature. These values include the starting current I
Start
, the nominal motor current
I
Mot.nom
, the maximum permissible startup time
(address
), the
number of permissible restart attempts under cold (n
cold
) and (n
warm
) conditions.
The starting current is entered at address
, expressed as a multiple of the nom-
inal motor current (
). For a correct interpretation of this parameter,
it is important that in Power System Data 1 the apparent power (address
) and the rated voltage (address
) of the motor are cor-
rectly set. The number of warm starts allowed is entered at address
(
), and the difference between the number of allowable cold and warm starts
(
) is entered at address
.
For motors without separate ventilation, the reduced cooling at motor stop can be
accounted for by entering at address
the reduced ventilation, expressed by the
factor
t at STOP. As soon as the current no longer exceeds the current flow
monitoring setting entered at address
, a motor standstill is
assumed and the time constant is increased by the set factor.
If no difference between the time constants is to be used (e.g. externally-ventilated
motors), then the factor should be set to
1
.
The cooling with the motor running is influenced by the extension
t at RUNNING. This
factor considers that motor running under load and a stopped motor do not cool down
at the same speed. It becomes effective as soon as the current exceeds the value set
at address
. With
1
the heating and the
cooling time constant are the same at operating conditions (I >
).
Setting Example:
Motor with the following data:
The ratio between the starting current and the motor nominal current is:
Settings
=
4.9
=
8.5 s
=
2
=
1
Nominal voltage
U
N
= 6600 V
Nominal current
I
Mot.nom
= 126 A
Starting current
I
Start
= 624 A
Starting time at I
START
T
START max
= 8.5 s
Permissible number of startups with
cold motor
n
cold
= 3
Permissible number of startups with
warm motor
n
warm
= 2
CT transformation ratio
200 A/1 A
I
Start
I
Mot.nom
⁄
624 A
126 A
---------------
4.95
4.9
≈
=
=