Functions
170
7UM62 Manual
C53000-G1176-C149-3
Minimum Voltage
Address
is used to set the minimum voltage below which the frequency
change protection will be blocked. A value of approx. 65 % U
N
is recommended. The
minimum voltage threshold can be deactivated by setting this address to „0“.
2.24.2.1 Settings of the Rate-of-Frequency-Change Protection
Table 2-12
Setting Value
stage dfn/dt
df/dt HYSTERESIS
(Addr. 4519A, 4521A)
dfx/dt M WINDOW
(Addr. 4520A, 4522A)
0.1...0.5 Hz/s
≈
0,05
25...10
0.5...1 Hz/s
≈
0,1
10...5
1...5 Hz/s
≈
0,2
10...5
5...20 Hz/s
≈
0,5
5...1
Addr.
Setting Title
Setting Options
Default Setting
Comments
4501
df/dt Protect.
OFF
ON
Block relay for trip com-
mands
OFF
Rate-of-frequency-change pro-
tection
4518
U MIN
10.0..125.0 V; 0
65.0 V
Minimum Operating Voltage
Umin
4519A
df1/2 HYSTERES.
0.02..0.99 Hz/s
0.10 Hz/s
Reset Hysteresis for df1/dt &
df2/dt
4520A
df1/2 M-WINDOW
1..25 Cycle
5 Cycle
Measuring Window for df1/dt &
df2/dt
4521A
df3/4 HYSTERES.
0.02..0.99 Hz/s
0.40 Hz/s
Reset Hysteresis for df3/dt &
df4/dt
4522A
df3/4 M-WINDOW
1..25 Cycle
5 Cycle
Measuring Window for df3/dt &
df4/dt
4502
df1/dt >/<
-df/dt< negative rate of freq.
change
+df/dt> positive rate of freq.
change
-df/dt< negative
rate of freq.
change
Mode of Threshold (df1/dt >/<)
4503
STAGE df1/dt
0.1..10.0 Hz/s;
∞
1.0 Hz/s
Pickup Value of df1/dt Stage
4504
T df1/dt
0.00..60.00 sec;
∞
0.50 sec
Time Delay of df1/dt Stage
4505
df1/dt & f1
OFF
ON
OFF
AND logic with pickup of stage f1
4506
df2/dt >/<
-df/dt< negative rate of freq.
change
+df/dt> positive rate of freq.
change
-df/dt< negative
rate of freq.
change
Mode of Threshold (df2/dt >/<)
4507
STAGE df2/dt
0.1..10.0 Hz/s;
∞
1.0 Hz/s
Pickup Value of df2/dt Stage
4508
T df2/dt
0.00..60.00 sec;
∞
0.50 sec
Time Delay of df2/dt Stage