Temperature Detection by Thermoboxes
275
7UM62 Manual
C53000-G1176-C149-3
9063
RTD 6 STAGE 1
-50..250
°
C;
∞
100
°
C
RTD 6: Temperature Stage 1
Pickup
9064
RTD 6 STAGE 1
-58..482
°
F;
∞
212
°
F
RTD 6: Temperature Stage 1
Pickup
9065
RTD 6 STAGE 2
-50..250
°
C;
∞
120
°
C
RTD 6: Temperature Stage 2
Pickup
9066
RTD 6 STAGE 2
-58..482
°
F;
∞
248
°
F
RTD 6: Temperature Stage 2
Pickup
9071A
RTD 7 TYPE
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 7: Type
9072A
RTD 7 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 7: Location
9073
RTD 7 STAGE 1
-50..250
°
C;
∞
100
°
C
RTD 7: Temperature Stage 1
Pickup
9074
RTD 7 STAGE 1
-58..482
°
F;
∞
212
°
F
RTD 7: Temperature Stage 1
Pickup
9075
RTD 7 STAGE 2
-50..250
°
C;
∞
120
°
C
RTD 7: Temperature Stage 2
Pickup
9076
RTD 7 STAGE 2
-58..482
°
F;
∞
248
°
F
RTD 7: Temperature Stage 2
Pickup
9081A
RTD 8 TYPE
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 8: Type
9082A
RTD 8 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 8: Location
9083
RTD 8 STAGE 1
-50..250
°
C;
∞
100
°
C
RTD 8: Temperature Stage 1
Pickup
9084
RTD 8 STAGE 1
-58..482
°
F;
∞
212
°
F
RTD 8: Temperature Stage 1
Pickup
9085
RTD 8 STAGE 2
-50..250
°
C;
∞
120
°
C
RTD 8: Temperature Stage 2
Pickup
9086
RTD 8 STAGE 2
-58..482
°
F;
∞
248
°
F
RTD 8: Temperature Stage 2
Pickup
9091A
RTD 9 TYPE
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 9: Type
Addr.
Setting Title
Setting Options
Default Setting
Comments