Rate-of-Frequency-Change Protection df/dt (ANSI 81R)
171
7UM62 Manual
C53000-G1176-C149-3
2.24.2.2 Information for the Rate-of-Frequency-Change Protection
4509
df2/dt & f2
OFF
ON
OFF
AND logic with pickup of stage f2
4510
df3/dt >/<
-df/dt< negative rate of freq.
change
+df/dt> positive rate of freq.
change
-df/dt< negative
rate of freq.
change
Mode of Threshold (df3/dt >/<)
4511
STAGE df3/dt
0.1..10.0 Hz/s;
∞
4.0 Hz/s
Pickup Value of df3/dt Stage
4512
T df3/dt
0.00..60.00 sec;
∞
0.00 sec
Time Delay of df3/dt Stage
4513
df3/dt & f3
OFF
ON
OFF
AND logic with pickup of stage f3
4514
df4/dt >/<
-df/dt< negative rate of freq.
change
+df/dt> positive rate of freq.
change
-df/dt< negative
rate of freq.
change
Mode of Threshold (df4/dt >/<)
4515
STAGE df4/dt
0.1..10.0 Hz/s;
∞
4.0 Hz/s
Pickup Value of df4/dt Stage
4516
T df4/dt
0.00..60.00 sec;
∞
0.00 sec
Time Delay of df4/dt Stage
4517
df4/dt & f4
OFF
ON
OFF
AND logic with pickup of stage f4
F.No.
Alarm
Comments
05503 >df/dt block
>BLOCK Rate-of-frequency-change prot.
05504 >df1/dt block
>BLOCK df1/dt stage
05505 >df2/dt block
>BLOCK df2/dt stage
05506 >df3/dt block
>BLOCK df3/dt stage
05507 >df4/dt block
>BLOCK df4/dt stage
05511 df/dt OFF
df/dt is switched OFF
05512 df/dt BLOCKED
df/dt is BLOCKED
05513 df/dt ACTIVE
df/dt is ACTIVE
05514 df/dt U< block
df/dt is blocked by undervoltage
05516 df1/dt pickup
Stage df1/dt picked up
05517 df2/dt pickup
Stage df2/dt picked up
05518 df3/dt pickup
Stage df3/dt picked up
05519 df4/dt pickup
Stage df4/dt picked up
05520 df1/dt TRIP
Stage df1/dt TRIP
05521 df2/dt TRIP
Stage df2/dt TRIP
05522 df3/dt TRIP
Stage df3/dt TRIP
05523 df4/dt TRIP
Stage df4/dt TRIP
Addr.
Setting Title
Setting Options
Default Setting
Comments