100–% Stator Earth Fault Protection with 20 Hz Voltage Injection (ANSI 64G - 100%)
199
7UM62 Manual
C53000-G1176-C149-3
Correction Angle,
Contact Resistance
The parameter
(default setting 0°) of address
is used to compen-
sate the angle error of the CTs and angle distortions caused by a less than ideal earth-
ing or neutral transformer. The correct setting for this parameter can only be deter-
mined with a primary test. The adjustment should be made for the tripping value.
The same is true for the transfer resistance of the earthing or neutral transformer. This
advanced parameter can be set with the DIGSI communication software (not possible
in local operation). As this resistance is normally negligible, a default setting
= 0
Ω
has been chosen for address
. However, the transfer resistance of the
voltage transformer is no longer negligible if the 20 Hz voltage is fed to a primary-side
loading resistor via a voltage transformer.
In large power units with generator circuit breaker, applications can be found where
there is some additional loading equipment on the low-voltage side of the unit trans-
former to reduce the influence by the zero voltage when the generator circuit breaker
is open. The 20 Hz source is connected via the neutral transformer in the generator
starpoint. With the generator circuit breaker closed, the protection measures the load-
ing resistance on the unit transformer side, which can be mistaken for an earth resis-
tance. The advanced parameter address
allows to set this additional loading
resistance. The default setting for
is
∞
. No additional loading resis-
tance is assumed.
2.29.2.1 Settings of the 100-% Stator Earth Fault Protection
Addr.
Setting Title
Setting Options
Default Setting
Comments
5301
100% SEF-PROT.
OFF
ON
Block relay for trip com-
mands
OFF
100% Stator-Earth-Fault Protec-
tion
5302
R< SEF ALARM
20..700 Ohm
100 Ohm
Pickup Value of Alarm Stage
Rsef<
5303
R<< SEF TRIP
20..700 Ohm
20 Ohm
Pickup Value of Tripping Stage
Rsef<<
5304
T SEF ALARM
0.00..60.00 sec;
∞
10.00 sec
Time Delay of Alarm Stage
Rsef<
5305
T SEF TRIP
0.00..60.00 sec;
∞
1.00 sec
Time Delay of Tripping Stage
Rsef<<
5306
SEF I>>
0.02..1.50 A
0.40 A
Pickup Value of I SEF>> Stage
5307
U20 MIN
0.3..15.0 V
1.0 V
Supervision Threshold of 20Hz
Voltage
5308
I20 MIN
5..40 mA
10 mA
Supervision Threshold of 20Hz
Current
5309
PHI I SEF
-60..60
°
0
°
Correction Angle for I SEF 100%
5310A
SEF Rps
0.0..700.0 Ohm
0.0 Ohm
Resistance Rps
5311A
Rl-PARALLEL
20..700 Ohm;
∞
∞
Ohm
Parallel Load Resistance