4 Technical Data
396
7UM62 Manual
C53000-G1176-C149-3
4.1.2
Power Supply
Direct Voltage
Voltage Supply Via Integrated Converter
Permissible AC Ripple Voltage,
peak to peak
≤
15 % of the power supply voltage
Power Consumption
7UM621
quiescent
Approx. 5.3 W
7UM622
Approx. 5.5 W
7UM621
energized
Approx. 12 W
7UM622
Approx. 15 W
Bridging Time for Failure/Short Circuit
≥
50 ms at V
≥
48 VDC (U
H,N
= 24/48 V)
≥
50 ms at V
≥
110 VDC (U
H,N
= 60..125 V)
≥
20 ms at V
≥
24 VDC (U
H,N
= 24/48 V)
≥
20 ms at V
≥
60 VDC (U
H,N
= 60..125 V)
Alternating Voltage
Voltage Supply via Integrated Converter
Power Consumption
7UM621
quiescent
Approx. 5.5 VA
7UM622
Approx. 5.5 VA
7UM621
energized
Approx. 13 VA
7UM622
Approx. 15 VA
Bridging Time for Failure/Short Circuit
≥
200 ms
4.1.3
Binary Inputs and Outputs
Binary Inputs
Number
7UM621
∗
–
7 (configurable)
7UM622
∗
–
15 (configurable)
Nominal Voltage Range
24 VDC to 250 VDC, bipolar
Current Consumption, Energized
Approx. 1.8 mA, independent of the
control voltage
Switching Thresholds
Adjustable voltage range with jumpers
Nominal Power Supply Direct Voltage V
PS nom
24/48 VDC
60/110/125 VDC
Permissible Voltage Ranges
19 to 58 VDC
48 to 150 VDC
Nominal Power Supply Direct Voltage V
PSnom
110/125/220/250 VDC
Permissible Voltage Ranges
88 to 300 VDC
Nominal Power Supply Alternating Voltage
V
PS
AC
115 V
AC
(50/60 Hz)
Permissible Voltage Ranges
92 to 132 V
AC