Installation Instructions
JATCO Environmental Protection Tank
J-7000
200
ABV
*INSTRUMENTATION GAS IS MANDATORY FOR SUPPLY GAS*
The JATCO Environmental Tank must be installed at a level which will allow the waste
liquids to be disposed of to gravity flow into the tank.
IMPORTANT: The top of the tank must be below the level of waste liquids to
be received.
Inlet and the outlet check valves are both teed from the same port near the bottom of the
tank (end opposite the sight glass). When facing this end, the inlet check valve is on the
left (
A)
and the outlet check valve
is on the right
(B)
.
The discharge should be piped directly to the storage tank that is to receive the waste liquid.
The discharge may be teed into an existing flow line, provided that a high-pressure check
valve (1000 psi)
is installed to prevent high pressure from returning to the discharge check
valve on the JATCO tank.
The tank supply gas must have adequate
volume
and pressure. For best operation use 1”
pipe for the tank supply gas plumed as close to the tank as possible. Then reduce down to the
tubing connections
(C)
and
(
J
)
on the JATCO tank.
This application requires two separate supply gas pressures. First supply gas pressure is
connected to the bottom inlet of the micro valve
(
C
)
this gas pressure must meet
7
0 psi and
not exceed 100 psi. Second supply gas pressure is connected to the 3-way ball valve
(
J
)
this gas pressure must not exceed 200 psi for normal operation. No pressure
regulator
is
provided.
Manual dump plunger
(F)
and gauge cock knobs are removed for shipping.
Manual Dump Plunger
(F)
: Install in ⅛” NPT hole in top of valve body
.
Note: The gland nut should be finger tight only.
Depressing the manual dump plunger
(F)
allows the operator to check function of the float
and micro valve. When the plunger is depressed, the tank will cycle once and return to the
automatic operation. The plunger button should be returned to the extended position.
3-way ball valve
(G)
is vented thru ½” NPT port
(H)
.
Liquid levels in the JATCO tank may be observed in the sight glass
(I)
furnished as standard
equipment.