453
AL.63 The writing parameter value using PR is out of range.
Alarm cause
Checking method
Corrective action
The writing parameter value of PR
command(TYPE=8) is out of
range.
Check whether the writing
parameter value is out of
range when writing the
parameter by PR
procedure.
Clear the alarm by
any of the following
solutions:
1.
Restart the
power.
2.
Press the "SET"
button at alarm
display screen.
3.
Turn on the RES
signal.
AL.64 The writing parameter using PR is wrong.
Alarm cause
Checking method
Corrective action
The PR program(TYPE=8) writes
the parameter during Servo ON.
The servo is on or setting
value is unreasonable
when writing the
parameter by PR
procedure
Adjust PR
commands and
parameters
AL.67 Motor temperature warning
Alarm cause
Checking method
Corrective action
The motor temperature is too high. Check the temperature of
motor.
The alarm will be
released
automatically after
the motor
temperature return
to normal.