297
No
Abbr.
Parameter function and description
Mode
Default
Range
Unit
PC17 ZSP Zero speed range:
Set the zero speed signal output speed range.
If the forward/reverse rotation motor speed is lower
than this parameter setting value, the DO:ZSP will be
on.
All
50
0
~
10000
rpm
mm/s
PC18
COP1
(*)
Stop option and power interruption & restart option
0 0 y x
x: power interruption and restart option
When power voltage is lower than allowable level,
insufficient voltage alarm occurs and servo motor
stops. When power voltage is normal and servo
motor will restart without alarm reset.
x=0: invalid x=1: valid
y: motor stop mode option.
Servo stop option in speed control mode.
y=1: motor stops immediately
y=0: motor decelerates to stop
All 0010h
0000h
~
0011h
N/A
PC19
COP2
(*)
Alarm history clear option and overload early warning
option.
0 z y x
x: alarm record clear.
When set to clear, the clear action will only be
activated after the power cycling, and it will be
automatically set to 0 after the clear is completed.
x=0: not clear alarm history
x=1: clear alarm history
y: overload early warning
y=0: no action when warning occurs.
All 0000h
0000h
~
0111h
N/A
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...