441
AL.19 Pr command error
Alarm cause
Checking method
Corrective action
The position
command counter
overflows.
Incremental system:
If in PR mode, the motor keeps running in
a single direction, it will cause the feedback
position register overflow and the
coordinate system fail to reflect the correct
position. This error occurs if the PR
absolute positioning command is issued at
this time.
Absolute system:
This error occurs when the absolute
positioning command is issued in the
following conditions:
1. The feedback position register
overflows.
2. The homing program has not been
executed after changing the E-Gear ratio
(PA06, PA07).
3. Execute absolute position command
when DO HOME signal is OFF.
Execute homing.
AL.20 Motor collision error
Alarm cause
Checking method
Corrective action
When the motor
current reaches the
value of PA15 and
the protection time of
PA16 has run out.
1.
Check if PA15 is valid.
2.
Check if PA15 setting is
too low, and if PA16 is too
small.
1.
Set PA15 to 0 if you open
it by mistake.
2.
When setting with actual
torque, if the setting is too
low, it will cause
malfunction, and if the
setting is too high, the
protection function will be
invalid.
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...