539
14.4.4.
Correct use
The use of equipment must comply with the specifications (voltage, temperature, etc. , please
refer to section 12.1 for details).
(1)
Power cable
Refer to section 3.1.6 for detailed power cable selection instruction.
Note 1: when connecting to the terminal block, use the screws included with the terminal
block.
Note 2: the letters in the table indicate crimping tools, please refer to the recommended
crimping terminal table for crimping terminals and suitable tools.
Note 3: the cable AWG selection depends on the specifications of the servo motor.
(2)
Fixed terminal block: crimp terminals must comply with UL specifications, and insulating
sleeves must be used to prevent direct contact.
Drive
Recommended torque(Nt-m)
R, S, T
U, V, W
+, -, P, P1, D, C, N
PE
SDP
-
200A4C
1.53
1.53
1.53
1.4
SDP
-
300A4C
SDP
-
500A4C
SDP
-
700A4C
(3)
Example of non-fuse circuit breaker selection
Drive
UL certified current-limiting circuit breaker
Example
SDP-010A2C
240 V, 5 A
NF50-SVFU 5A
SDP-020A2C
SDP-040A2C
240 V, 10 A
NF50-SVFU 3P 10A
SDP-075A2C
240 V, 15 A
NF50-SVFU 3P 15A
SDP-100A2C
SDP-150A2C
240 V, 30 A
NF50-SVFU 3P 30A
SDP-200A2C
SDP-300A2C
SDP-200A4C
480 V, 20 A
NF125-SVU 3P 20A
SDP-300A4C
480 V, 30 A
NF125-SVU 3P 30A
SDP-500A4C
480 V, 60 A
NF125-SVU 3P 60A
SDP-700A4C
480 V, 70 A
NF125-SVU 3P 70A
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...