Table 8.1 Digital input (DI) descriptions
DI name
Setting
value
Description
SON
0x01
When this signal is turned on, the servo is on.
RES
0x02
When alarm occurs, some of alarm can be released by turning on this
signal.
PC
0x03
When this signal is on, it switches the speed controller from proportion
integral type to proportion type.
TL
0x 04
When this signal is on, the analog torque limit is valid.’
When this signal is off, the inner torque limit 1 is valid.
TL1
0x 05
When this signal is on, the inner torque limit 2 is invalid.
SP1
0x 06
Speed control option 1
SP2
0x 07
Speed control option 2
SP3
0x 08
Speed control option 3
ST1/RS2
0x 09
In speed mode, when this signal is on, it will activate forward speed
command.
In torque mode, when this signal is on, it will activate reverse torque
command.
ST2/RS1
0x0A
In speed mode, when this signal is on, it will activate reverse speed
command.
In torque mode, when this signal is on, it will activate forward torque
command.
ORGP
0x0B
In internal register position mode, when searching for the origin, the
servo uses this position as the homing origin by turning on this signal.
SHOM
0x0C
In internal position register mode, when searching for the origin, origin
searching function is activated by turning on this signal.
CM1
0x0D
In position mode, it is E-Gear ratio numerator option 1.
CM2
0x0E
In position mode, it is E-Gear ratio numerator option 2.
CR
0x0F
When this signal is on, it clears the position control counter deviation
pulses on its leading edge. The pulse width should be over 10ms.
CDP
0x10
When this signal is on, it switches all the gain values to the multiplier of
PB14~PB17 setting.
LOP
0x11
It used to switch control modes in multi-mode.
EMG
0x12
When this signal is off, servo is in emergency status.
You can turn on this signal to release the emergency status.
POS1
0x13
Position command option 1 in internal register position mode.
POS2
0x14
Position command option 2 in internal register position mode.
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...