161
6.3.5.
Gain adjustment of the speed loop
In the Speed control loop, you can adjust many different gain parameters. You can adjust the
gain automatically or manually which is set by PA02. If set as auto adjustment, the load inertia
ratio will be estimated continuously and the control gain value will be set automatically. If set
as manual adjustment, you should manually set proper load inertia ratio and control gain value,
and all auto or auxiliary functions will be disabled. The structure diagram of the speed loop is
shown in the following figure:
In the speed control loop, the gain adjustment related parameters are summarized as follows:
Name
Parameter
abbreviation
Parameter
code
Setting
range
Unit
Default
value
Control
mode
Auto-tuning
mode setting
ATUM
PA02
0000h~0004h N/A
0002h
Pt, Pr, S,
T
Auto-tuning
response level
setting
ATUL
PA03
1~32
N/A
10
Pt, Pr, S,
T
Speed loop
gain
VG1
PB08
40~9000
rad/s
183
Pt, Pr, S
Speed integral
gain
VIC
PB09
1~1000
ms
34
Pt, Pr, S
Speed feed-
forward gain
VFG
PB10
0~200
%
0
S
Auto mode:
The servo drive will adjust the optimal controller gain during acceleration and deceleration.
And its detail description can refer to section 5.3.2.
Manual mode:
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...