168
are resonance attenuation rates. When low-frequency resonance occurs, the user can set
PB29 to 1 to enable the auto-suppression function if the resonance frequency is unknown,
the drive will automatically detect the resonance frequency, and then set the detected
results to the PB31 and PB33 in sequence, and set PB32, PB34 to 1 to enable the auto-
suppression function. After auto-detection is completed, PB29 will set back to 0
automatically. For other PB29 operate procedure, please refer to the table below.
When PB29 is set to 1, if the resonance still exists, please check whether PB32 and PB34
are both 0. If yes, it means the vibrate frequency is not detected, which may impacted by
high swing detection level(Note2). You can decrease the level and restart the detection to
solve. If the values are not 0, which means the detection is wrong, which may cause by low
swing detection level. You can increase the level before restart the detection. The complete
auto-suppression flow chart is as follows:
Note 1. Too large gain value may make the motor to run un-smoothly.
Note 2. The swing detection level refers to the peak-to-peak value of the vibration, and the
unit is pulse.
PB29 parameter flow chart
PB29 current
value
PB29 modified
value
Function
0
1
Clear PB31~34 values,
enable the auto-suppression mode
1
0
Store PB31~34 value,
disable the auto-suppression function.
1
1
Clear PB31~34 values,
enable the auto -suppression mode
Flow chart of auto-resonance suppression.
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...