ADDENDUM TO THE CFW-10 FREQUENCY INVERTER USER MANUAL 

CFW-10 COLD PLATE

 

08/2006 

 

 

 

ATTENTION! 

Information presented in this addendum applies only to CFW-10 models with special hardware (CP). hence, check 
if the “CP” tag appears on the intelligent code of the product identification sticker.

 

 
This special hardware “CP” was designed in order to allow mounting the “CP” CFW-10 frequency inverter in any heat 
dissipation surface, since following recommendations are fulfilled. 
 

INSTALLATING THE FREQUENCY INVERTER ON THE HEAT DISSIPATION SURFACE - STEPS.

 

1. 

Mark out the positions of the mounting holes on the backing plate where the frequency inverter will be located (see in 
figure 1 drawing and hole size). 

2. 

The surface that is in contact with frequency inverter dissipation surface must be free of dirt and burr. Standard 
requirements are: The backing plate flatness (considering an area of 100mm

2

)

 

shall be less than 50

μ

m and the 

roughness less than 10

μ

m.

 

3. 

Use (M4) mounting screws in order to fasten the frequency inverter to the base plate 

 

 MOUNTING BASE VIEW                FRONTAL VIEW                                 SIDE VIEW 

 

Figure 1

 – Dimensional and mounting holes 

 

 

4. 

After drilling the holes, clean the contact surface of the backing plate and coat it with a thin thermal paste layer, or with a 
heat conducting foil or similar product (approx. 100

μ

m).  

5. 

Continue the mechanical installation as indicated in Chapter 3.1 of the frequency inverter user manual. 

 

Note!

 

Table 3.2 of the user manual shall not be considered for this special frequency inverter. External dimensions a
mounting holes are according to the figures of this addendum. 

 

6. 

Electrical installation shall be performed as indicated in the Chapter 3.2 of the frequency inverter user manual. 

 

 

ATTENTION!

 

After operation, check P008. This parameter must not exceed 90ºC. 
 

Dimensions 

Fixinf Base 

Model 

Width 

(mm) 

Height 

(mm) 

Depth 

(mm) 

(mm) 

(mm) 

(mm) 

(mm) 

Mounting 

Screw 

Weight 

[Kg] 

Degree of 

Protection 

1.6A/200-240V 100  132 

82 

90  120 

M4 

0.7 

IP20 

2.6A/200-240V 100  132 

82 

90  120 

M4 

0.7 

IP20 

4.0A/ 200-240V 

100 

132 

82 

90 

120 

M4 

0.7 

IP20 

7.3A/200-240V 120  161 

82 

110  149 

M4 

1.0 

IP20 

10.0A/200-240V 120  191 

82 

110  179 

M4 

1.2 

IP20 

1.6/110-127V 100  132  82  90  120  5 

M4 

0.7 

IP20 

2.6/110-127V 100  132  82  90  120  5 

M4 

0.7 

IP20 

4.0/110-127V 100  161  83  110  149  5 

M4 

1.0 

IP20 