AL.2F Regenerative energy error
Alarm cause
Checking method
Corrective action
When the regenerative
load rate exceeds 100%.
1.
Check if the
acceleration/deceleration
time is too short.
2.
Check if the frequency of
forward and reverse
rotation is too fast.
1.
Adjust the
acceleration
/deceleration time, or
reduce the frequency
of forward and reverse
rotation.
2.
Press SET button in
current alarm screen
display.
3.
Restart the power.
AL.30 Pulse output frequency excess
Alarm cause
Checking method
Corrective action
Detector output error which is
caused by encoder error.
Check the error history to
see whether it is
accompanied with an
encoder error (AL0B,
AL0C, AL22, AL26, AL27).
Follow the
corrective action of
AL.0B, AL.22,
AL.26, AL.27.
The output pulse exceeds the
hardware allowable range.
Check whether the
following conditions exist:
(a) Motor feedback
speed> PA41.
(b) (Motor speed/60) *
detector output pulse
number per revolution >
20x10
6
Correctly set PA41
and PA14: PA41>
motor speed and
(motor speed/60)*
the detector output
pulse number per
revolution <20x10
6
AL.31
Over current 2
Alarm cause
Checking method
Corrective action
The drive current feedback is
abnormal.
Restart the drive. If the issue persists, send your
servo drive back to the distributor or manufacturer.
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...